Architectural/Engineering
Specifications

Smoke detector shall be a System Sensor i³ Series model

number ________, Listed to Underwriters Laboratories UL

268 Fire Protection Signaling Systems. The detector shall be a

photoelectric type (models 2W-B, 4W-B) or a combination pho-

toelectric/thermal (models 2WT-B, 4WT-B) with thermal sensor

rated at 135°F (57.2°C). The detector shall include a mounting

base for mounting to 3.5" (88.9 mm) and 4" (101.6 mm) octag-

onal, single-gang, and 4" (101.6 mm) square backboxes with a

plaster ring, or directly mount to the ceiling using drywall

anchors. Wiring connections shall be made by means of

SEMS screws. The detector shall allow pre-wiring of the base

and the head shall be a plug-in type. The detector shall have a

nominal sensitivity of 2.5%/foot (0.762%/meter) as measured

in the UL smoke box. The detector shall be capable of auto-

matically adjusting its sensitivity by means of drift compensa-

tion and smoothing algorithms. The detector shall provide

dual-color LED indication which blinks to indicate power-up,

normal standby, out-of-sensitivity, alarm, and freeze trouble

(models 2WT-B, 4WT-B) conditions. When used in conjunction

with the 2W-MOD module, two-wire models shall include a

maintenance signal to indicate the need for maintenance at

the alarm control panel, and shall provide a loop testing capa-

bility to verify the circuit without testing each detector individu-

ally.

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.

UL/ULC Listed: S911

• FM Approved

CSFM: 7272-1653:152

MEA: 290-01-E

Maryland State Fire Marshal: Permit # 2093

Product Line Information

2W-B: Two-wire photoelectric smoke detector.
C2W-BA: Same as 2W-B, ULC listing.
2WT-B: Two-wire photoelectric smoke detector with 135°F

(57.2°C) fixed thermal sensor.
C2WT-BA: Same as 2WT-B, ULC listing.
4W-B: Four-wire photoelectric smoke detector.
C4W-BA: Same as 4W-B, ULC listing.
4WT-B: Four-wire photoelectric smoke detector with 135°F

(57.2°C) fixed thermal sensor.
C4WT-BA: Same as 4WT-B, ULC listing.

ACCESSORIES:

2W-MOD2: Two-wire loop test/maintenance module.
SENS-RDR: Sensitivity reader.
A77-AB2: Retrofit adapter bracket, 6.6” (167.7cm) diameter.