General specifi cations, N x g – Notifier FD Series UV/IR Flame Detector User Manual

Page 3

Advertising
background image

General Specifi cations

Standard Specifications

Operating Voltage Range

10 to 32 V

DC

Power Consumption

A Version:

Nominal 35 mA / 0.84 W | Maximum 65 mA / 1.6W (at 24 V

DC

)

Nominal 78 mA / 1.88 W | Maximum 112 mA / 2.7W (with heater)

AR Version: Nominal 52 mA / 1.25 W | Maximum 84 mA / 2.02W (at 24 V

DC

)

Nominal 98 mA / 2.35 W | Maximum 130 mA / 3.12W (with heater)

Temperature Range

Certified -40°C to +75°C (-40°F to +167°F)

Operational -50°C to +75°C (-58°F to +167°F)

Field of View

120° horizontal / 95° vertical @ 50% of maximum on axis distance

Spectral Range

UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms) | IR Radiation in the 4.4 micron range

Time Delay

DIP switch selectable to 0, 3, 5, 7 seconds

Sensitivity Settings

DIP switch selectable to 8, 16, 24 or 32 counts per second

Typical Response Time

<6 seconds depending on fuel source, fire size and distance

Enclosure Material

Anodized, copper-free aluminum (optional stainless steel) factory sealed housing

Humidity Range

0 to 95% RH, non-condensing

Weight (with swivel)

2.1 kg / 4.5 lb. (stainless steel option 3.4 kg / 7.5 lb.)

Outputs

A Version:

0 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V dc or 150 Ohms at 11.0 V

DC

Non-isolated loop supply

AR Version: Form C contacts rated 1 Amp at 30 V

DC

, 0.5 Amp at 125 V

AC

Selectable

energized/de-energized, latching/non-latching fire relay

Fault relay factory set as energized/non-latching, cannot be modified

Certifications

CSA and NRTL/C certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature code T5

Enclosure type NEMA 4X, IP67. Ex d II B+H2 T5 (Class I, Zone 1, Grp II B+H2 T5)

For Canada only: CSA certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature code T5

Enclosure type NEMA 4X. Ex d II B+H2 T5. CE Ex II 2 G, Ex d II B+H2 T5

Factory Mutual (FM) flame detector performance certification FM3260

n X g

2.50”

0.25”

4.12”

2.96”

2.60”

5.89”

3/4” NPT

(63.5 mm)

(6.4 mm)

(66.0 mm)

(104.7 mm)

(149.6 mm)

(75.2 mm)

Centre Line

Yellow Dot

VI Reflector

VI Emitters

Summary of Distances

Fuel Fire

Size

Typical

Response

n-heptane

1 ft. x 1 ft.

< 11sec @ 140 ft.

gasoline

1 ft. x 1 ft.

< 6sec @ 120 ft.

methane

30 in. plume

< 6sec @ 100 ft.

Immunity False Alarm Stimuli

Stimuli Immunity

Range

Direct/indirect sunlight

Total

1500W heater

10 ft.

Halogen, incandescent light

3 ft.

Florescent light

10 ft.

Arc welding (unmodulated)

10 ft.

Lightning Total

FD Series UV IR.indd 3

4/20/2009 10:26:51 AM

Advertising