Ordering information, Wiring diagrams – Notifier AH Series User Manual

Page 2

Advertising
background image

Page 2 of 4 — DN-5566 • 03/30/04

PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING, OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS,
CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.

ORDERING INFORMATION

*Refer to data sheet DN6111 for Mounting Options
NOTE: Due to continous development of our products, specifications and offerings are subject to change without
notice in accordance with Notifier’s standard terms and conditions

MODEL

INPUT

VOLTAGE

VDC

REGULATED

VOLTAGE

RANGE

VDC/FWR

STROBE

CANDELA

(cd)

AS-24MCW

24

16.0 - 33.0

15/30/75/110

AS-241575W

24

16.0 - 33.0

15 (75 on axis)

AS-121575W

12

8.0 - 17.5

15 (75 on axis)

AS-24MCC

24

16.0 - 33.0

15/30/75/95

ASWP-2475W

24

16.0 - 33.0

75 @ -31°F

TABLE 1: RATINGS PER UL 1971

DESCRIPTION

VOLUME

REVERBERANT

DBA PER UL

464 @ 10 FT.

ANECHOIC

DBA

@ 10 FT.

High

91

99

Medium

88

95

Low

83

90

High 87

99

Medium

84

95

Low

79

90

TABLE 2: DBA RATINGS FOR 12 VDC & 24 VDC SERIES

AS/AH 12 & 24 VDC AUDIBLE

Continuous

Horn

Code 3 Horn

UL MEA CSFM FM BFP

AS-24MCW-FR

15/30/75/110

X

X

24

WALL

A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

X

AS-24MCW-FW

15/30/75/110

X

X

24

WALL

A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

X

AS-241575W-FR

15 (75 on Axis)

X

X

24

WALL

A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

AS-121575W-FR

15 (75 on Axis)

X

X

12

WALL

A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

AS-24MCC-FW

15/30/75/95

X

X

24

CEILING

A,B,D,E,F,G,H,J,N,O,R,X X

X

X

*

*

ASWP-2475W-FR

75 @ -31°F

X

X

24

WALL

I

X

X

X

X

X

AH-24-R

-

X

X

24

WALL/CEILING A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

X

AH-12-R

-

X

X

12

WALL/CEILING A,B,D,E,F,G,H,J,N,O,R,X X

X

X

X

X

AH-24WP-R

-

X

X

24

WALL/CEILING

K

X

X

X

X

X

AH-12-WP-R

-

X

X

12

WALL/CEILING

K

X

X

X

X

X

VDC

WALL/

CEILING

MOUNT

MOUNTING

OPTIONS*

AGENCY APPROVALS

MODEL

STROBE

CANDELA

NON-

SYNC

SYNC

W/SM,

DSM

NOTES:
SM Sync Module is rated for 3.0 amperes @ 24 VDC.
DSM Sync Module is rated for 3.0 amperes per circuit. The
maximum number of interconnected DSM modules is twenty
(20).

M ODEL

NUM BER

INP UT

VOLTAGE

(VDC)

AVERAGE

M EAN

CURRENT

@ 24 VDC

M OUNTING

OP TIONS

SM-12/24-R

24

.028

W

DSM-12/24-R

24

.035

W

SYNC MODELS/POWER SUPPLY

AS devices synchronized with SM Module single Class
“B” (Style Y) circuit
WITH
audible silence feature.

WIRING DIAGRAMS

AS device non-synchronized.

Advertising