SpectrAlert® Advance

Indoor Selectable Output Speaker Strobes and
Dual Voltage Evacuation Speakers

Audio/Visual Devices

DN-60327:B1

General

The SpectrAlert Advance Series of speakers and speaker

strobes is designed to reduce ground faults. The plug-in design

allows the installer to pre-wire mounting plates and dress the

wires before plugging in the speakers. The plastic cover pre-

vents nicked wires by covering exposed speaker components.
This design also allows faster installations with instant feedback

to ensure that wiring is properly connected; rotary switches to

select voltage and power settings; and 11 field selectable can-

dela settings for wall and ceiling speaker strobes.
The low total harmonic distortion of the SP speaker offers high

fidelity sound output while the SPV speaker offers high volume

sound output for use in high ambient noise applications.
SpectrAlert Advance makes installation easy
• Attach a universal mounting plate to a 4” x 4” x 2-1/8” back

box. Flush mount applications are achievable without the

need for an extension ring.

• Connect the notification appliance circuit or speaker wiring to

the PEMS terminals on the mounting plate.

• Attach the speaker or speaker strobe to the mounting plate

by inserting the product tabs into the mounting plate grooves.

Rotate the device into position to lock the product pins into

the mounting plate terminals. The device will temporarily hold

in place with a catch until it is secured with a captured mount-

ing screw.

Features

• Plug-in design
• Protective cover isolates speaker components, reduces

ground faults

• Electrical compatibility with existing SpectrAlert products
• Field selectable candela settings on wall and ceiling units:

Standard: 15, 15/75, 30, 75, 95, 110, 115
High: 135, 150, 177, 185

• Shorting spring on mounting plate tests continuity before

installation

• Rotary switch simplifies field selection of speaker voltage and

power settings

• Universal mounting plate for wall- and ceiling-mount units
• Compatible with System Sensor synchronization protocol
• SP speakers offer high fidelity sound output
• SPV speakers offer high volume sound output
• Automatic selection of 12 or 24 volt operation at 15 and 15/75

candela

• No extension ring required
• Ceiling and wall mount application
• Optional tamper resistant Torx head screw included

Specifications

PHYSICAL SPECIFICATIONS

Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
Dimensions, Wall-Mount: –

SPS Speaker Strobe: 6.0”L x 5.0”W x 4.7”D (includes lens

and speaker)

SPSV Speaker Strobe: 6.0”L x 5.0”W x 4.9”D (includes

lens and speaker)

SP Speaker: 6.0”L x 5.0”W x 2.8”D
SPSV Speaker: 6.0”L x 5.0”W x 2.9”D

Dimensions, Ceiling-Mount:

SPS Speaker Strobe: 6.8”Dia x 4.7”D (includes lens and

speaker)

SPSV Speaker Strobe: 6.8”Dia x 4.8”D (includes lens and

speaker)

SP Speaker: 6.8”Dia x 2.8”D
SPSV Speaker: 6.8”Dia x 2.9”D

ELECTRICAL/OPERATING SPECIFICATIONS

Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage (speakers): 50VDC
Strobe Flash Rate: 1 flash per second
Nominal Voltage (strobes): Regulated 12VDC/FWR or regu-

lated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with

built-in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V

nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V

nominal) or 17 to 33V (24V nominal)
Frequency Range: 400 to 4000 Hz
Power: ¼, ½, 1, 2 watts

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain

approval agencies, or listing may be in progress. Consult fac-
tory for latest listing status.

UL/ULC Listed: S4048

MEA: 10-08-E

CSFM: 7320-1653:201