Page 2 of 6 — DN-60517:A • 06/02/2009

cans with Disabilities Act requirements for visible signaling

appliances, flashing at 1 Hz over the strobe’s entire operating

voltage range. The strobe light shall consist of a xenon flash

tube and associated lens/reflector system.

HORN STROBE COMBINATION

The horn strobe shall be a System Sensor SpectrAlert

Advance Model _______ listed to UL 1971 and UL 464 and

shall be approved for fire protective service. The horn strobe

shall be wired as a primary-signaling notification appliance

and comply with the Americans with Disabilities Act require-

ments for visible signaling appliances, flashing at 1 Hz over

the strobe’s entire operating voltage range. The strobe light

shall consist of a xenon flash tube and associated lens/reflec-

tor system. The horn shall have three audibility options and

an option to switch between a temporal three-pattern and a

non-temporal (continuous) pattern. These options shall be

set by a multiple position switch. The horn and horn strobe

models shall operate on a coded or non-coded power supply.

SPEAKER STROBE COMBINATION

The speaker strobe shall be a System Sensor SpectrAlert

Advance Model __________ listed to UL 1480 and UL 1971

and be approved for fire protective signaling systems.

Speaker shall be capable of operating at 25.0 or 70.7 nomi-

nal Vrms selected via rotary switch, and shall have a fre-

quency range of 400 to 4000 Hz. Speaker shall have power

taps that are selected by rotary switch. The strobe shall com-

ply with the NFPA 72 requirements for visible signaling appli-

ances, flashing at 1 Hz over the strobe’s entire operating

voltage range. The strobe light shall consist of a xenon flash

tube and associated lens/reflector system.

OUTDOOR PRODUCTS

SpectrAlert Advance outdoor strobes, horn strobes and

speaker strobes shall be listed for outdoor use by UL and

shall operate between –40°F and 151°F (–40°C and 66°C).

The products shall be listed for use with a System Sensor

outdoor/weatherproof back box with half-inch and three-

fourths-inch conduit entries.

SYNCHRONIZATION MODULE

The module shall be a System Sensor Sync•Circuit model

MDL3R or MDL3W listed to UL 464 and shall be approved for

fire protective service. The module shall synchronize Spec-

trAlert strobes at 1 Hz and horns at temporal three. Also,

while operating the strobes, the module shall silence the

horns on horn strobe models over a single pair of wires. The

module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch (11.90

x 11.90 x 5.40 cm) back box. The module shall also control

two Style Y (class B) circuits or one Style Z (class A) circuit.

The module shall synchronize multiple zones. Daisy chaining

two or more synchronization modules together will synchro-

nize all the zones they control. The module shall not operate

on a coded power supply.

COLOR LENS STROBE ATTACHMENT

The System Sensor SpectrAlert Advance color lens attach-

ments shall be approved for fire protective service as listed in

UL 1638. The lens attachments shall only be used with (plain

non-fire-printed) System Sensor strobe devices. They shall

mount to any wall or ceiling strobe and be rated from –35°F

to 151°F (-37°C to 66°C).

Specifications

PHYSICAL SPECIFICATIONS

Standard Operating Temperature: 32°F to 120°F (0°C to

49°C)
K Series Operating Temperature: -40°F to 151°F (-40°C to

66°C)
Humidity Range: 10 to 93% non-condensing (indoor mod-

els)
Dimensions:

– Wall-Mount Strobe and Horn Strobe (including lens):

5.6” L x 4.7” W x 2.5” D

– SPS Speaker Strobe (including lens and speaker):

6.0” L x 5.0” W x 4.7” D

– Ceiling-Mount Strobe (including lens): 6.8” diameter

x 2.5” D

ELECTRICAL/OPERATING SPECIFICATIONS

Nominal Voltage (strobes and horn strobes): Regulated

12 DC/FWR or regulated 24 DC/FWR
Nominal Voltage (speakers): 25 V or 70.7 V (nominal)
Maximum Supervisory Voltage (speakers): 50 VDC
Operating Voltage Range: 8 to 17.5 V (12 V nominal) or 17

to 33 V (24 V nominal)
Strobe Flash Rate: 1 flash per second
Speaker Frequency Range: 400 to 4000 Hz
Speaker Power: ¼, ½, 1, 2 watts

SPEAKER SOUND OUTPUT

UL CURRENT DRAW DATA

UL Reverberant (dBA @ 10 ft.) 2W

1W

1/2W

1/4W

Wall-Mount SPS Series

85

82

79

76

Wall-Mount SPV Series

90

87

84

81

Ceiling-Mount SPC Series

86

83

80

77

Ceiling-Mount SPCV Series

90

87

84

81

UL Max. Strobe Current Draw (mA RMS)

8–17.5 Volts

16–33 Volts

Candela

DC FWR DC FWR

Standard Can-
dela Range

15* 123

128

66

71

15/75* 142 148 77 81

30* NA

NA 94

96

75* NA

NA 158

153

95* NA

NA 181

176

110 NA

NA 202

195

115 NA

NA 210

205

High Candela
Range

135 NA

NA 228

207

150 NA

NA 246

220

177 NA

NA 281

251

185 NA

NA 286

258

Advertising