Notifier Selectable Output Notification Appliances User Manual

Spectralert, Advance, Selectable output notification appliances

Advertising
background image

DN-7087:C1 • 11/9/11 — Page 1 of 4

SpectrAlert

®

Advance

Selectable Output
Notification Appliances

Audio/Visual Devices

DN-7087:C1

General

System Sensor® SpectrAlert® Advance selectable-output

horns, strobes and horn/strobes are rich with features guaran-

teed to cut installation times and maximize profits. The Spec-

trAlert Advance series of notification appliances is designed to

simplify your installations, with features such as: plug-in

designs, instant feedback messages to ensure correct installa-

tion of individual devices, and eleven field-selectable candela

settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first

attach a universal mounting plate to a four-inch square, four-

inch octagon, or double-gang junction box. The two-wire

mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the

SEMS terminals on the mounting plate.
Finally, attach the horn, strobe, or horn/strobe to the mounting

plate by inserting the product’s tabs in the mounting plate’s

grooves. The device will rotate into position, locking the prod-

uct’s pins into the mounting plate’s terminals. The device will

temporarily hold in place with a catch until it is secured with a

captured mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts.
• 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can-

dela by way of a rear-mounted slide switch and front view-

ing window.

• Horn tones and volume by way of a rotary switch.
• The SpectrAlert Advance series includes outdoor notifica-

tion appliances. Outdoor strobes and horn/strobes (two-

wire and four-wire) are available for wall or ceiling. Outdoor

horns are available for wall only. All System Sensor outdoor

products are rated between –40°F and 151°F (–40°C and

66°C) in wet or dry applications.

Models available:
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire

horn/strobe.

• Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire

horn/strobe.

• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-

wire horn/strobe.

• Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire

horn/strobe.

Features

• Plug-in design.
• Same mounting plate for wall- and ceiling-mount units.
• Shorting spring on mounting plate for continuity check

before installation.

• Captive mounting screw.
• Tamper-resistance capability.
• Field-selectable candela settings on wall and ceiling units:

15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.

• Automatic selection of 12 or 24 volt operation at 15 and 15/

75 candela.

• Outdoor wall and ceiling products.

• Outdoor products rated from –40°F and 151°F (–40°C and

66°C).

• Outdoor products rainproof per UL50 (NEMA 3R) and

weatherproof per NEMA 4X, IP56

• Minimal intrusion into the backbox.
• Horn rated at 88+ dbA at 16 volts.
• Rotary switch for tone selection.
• Three horn volume settings.
• Electrically compatible with existing SpectrAlert products.

Engineering Specifications

SpectrAlert Advance horns, strobes, and horn/strobes shall

mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81

cm) backbox, 4.0" (10.16 cm) octagonal backbox, or a double-

gang backbox. Two-wire products shall also mount to a single-

gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A

universal mounting plate shall be used for mounting ceiling

and wall products. The notification appliance circuit wiring

shall terminate at the universal mounting plate. Also, Spec-

trAlert Advance products, when used with the Sync•Circuit™

Module accessory, shall be powered from a non-coded notifi-

cation appliance circuit output and shall operate on a nominal

12 or 24 volts. When used with the Sync•Circuit Module, 12-

volt rated notification appliance circuit outputs shall operate

between 9 and 17.5 volts; 24-volt rated notification appliance

circuit outputs shall operate between 17 and 33 volts. Indoor

SpectrAlert Advance products shall operate between 32°F and

120°F (0°C and 49°C) from a regulated DC, or full-wave-recti-

fied, unfiltered power supply. Strobes and horn/strobes shall

have field-selectable candela settings including 15, 15/75, 30,

75, 95, 110, 115, 135, 150, 177, 185.

Indoor Ceiling

Horn/Strobe

Outdoor Ceiling

Strobe

Indoor Wall

Horn/Strobe

Indoor Ceiling

Strobe

Indoor Wall

Horn

Outdoor Wall

Strobe