Notifier Wheelock NH Series Horns User Manual

Page 2

Advertising
background image

Page 2 of 4 — dn-6601:a • 10/16/09

Continuous
Horn

High

83

87

89

95

Low

76

81

84

90

Code 3 Horn

High

79

82

89

95

Low

72

76

84

90

Table 3: *Average RMS Current Ratings

NS-24MCW with High (95 dBA) Setting

Voltage

15cd

30cd

75cd

110cd

16.0 VDC

.077

.113

.195

.268

24.0 VDC

.065

.087

.134

.174

33.0 VDC

.069

.085

.117

.134

NS-24MCW with Low (90 dBA) Setting

Voltage

15cd

30cd

75cd

110cd

16.0 VDC

.070

.106

.188

.261

24.0 VDC

.052

.072

.126

.158

33.0 VDC

.045

.060

.097

.114

* Average RMS Current is per UL average RMS method and
Average Mean Current is per UL average mean method. NH

models use average mean current. For rated in Rush and Peak

current across UL Listed voltage range for both filtered DC and

VRMS (FWR), see installation instructions.

Table 2: dBA Ratings for Series NS/NH Horn

Table 4: *Average RMS Current Ratings

NS-241575W

Voltage

High (95) dBA

Low (90) dBA

16.0 VDC

.120

.116

24.0 VDC

.094

.093

33.0 VDC

.102

.078

Table 5: *Average Mean Current Ratings NH Horn 24

Volt Models

Voltage

High (95) dBA

Low (90) dBA

16.0 VDC

.019

.017

24.0 VDC

.028

.022

33.0 VDC

.039

.027

Table 6: Sync Models/Power Supply

Model

Number

Input

Voltage

(VDC)

Average

Mean

Current

@ 24 VDC

Mounting

Options

SM-12/24-R

24

.028

W

DSM-12/24-R

24

.035

W

NOTE: SM Sync Module is rated for 3.0 amperes @ 24 VDC.
DSM Sync Module is rated for 3.0 amperes per circuit. The max-
imum number of interconnected DSM Modules is twenty (20).

Table 7: UL Maximum Current**

Series NS/NH

24 VDC

Audible

Wall Mount Strobe Models

NH-12/24

NS-241575W

NS-24MCW

@24VDC

15/75cd

15cd

30cd

75cd

110cd

High (95) dBA

24VDC

.044

.104

.074

.107

.184

.244

Low (90) dBA

24VDC

.018

.096

.066

.101

.177

.232

Series NS/NH

12 VDC

Audible

Wall Mount

** RMS current ratings are per UL average
RMS method. UL max current rating is the max-
imum RMS current within the listed voltage
range (16-33V for 24V units). For strobes, the
UL max current is usually at the minimum listed
voltage (16V for 24V units). For audibles, the
max current is usually at the listed voltage (33V
for 24V units). For unfiltered FWR ratings, see
installation instructions.

NH-12/24

Aud/Strobe

@12VDC

NS-121575W

High (95) dBA

12VDC

.021

.220

Low (90) dBA

12VDC

.012

.210