Page 2 of 4 — DN-6940:B1 • 8/31/2011

LCD-160 Interface and Indicators

The liquid crystal display is 40 characters wide and 16 lines

deep, and displays all programming screens and other infor-

mation. The keypad is functional only when an entry is

requested by the system. Enter or change fields and issue

commands on the display by using the two types of keys on

the keypad: fixed function and soft keys.
Fixed function keys are the ten keys labeled on the front of

the LCD-160, operating at all times on all screens unless oth-

erwise noted. With both an active command center and DCC

enabled at the panel, Acknowledge, Signal Silence, System

Reset, and Drill require permission before they can be pro-

cessed.
Acknowledge: Press to respond to any event or trouble sig-

nal. If enabled, silences the LCD-160 piezo sounder. Sends an

acknowledge message to the panel.
Signal Silence: Press to send a system silence command to

the panel, with the particular silencing action information

stored at the FACP. Verification screen appears on networked

displays.
System Reset: Press to send a system reset command to the

panel, with the particular reset action information stored at the

FACP. Verification screen appears on networked displays.
Drill: Press (hold for two seconds) to activate all silenceable

fire output circuits.
Lamp Test: Press to test the LED indicators and the piezo, or

display firmware version numbers.
Fire Alarm: Scroll/display a list of associated events.
Security: Scroll/display a list of associated events.
Supervisory: Scroll/display a list of associated events.

Trouble: Scroll/display a list of associated events.
Other Event: Scroll between prealarm and disabled events.
For complete information on key functions and effects on dif-

ferent panels, refer to the LCD-160 Manual and panel manu-

als.
Soft keys are the six keys to the right and left of the display.

Use them to select commands that appear on the display for

each different screen. Refer to the screens in the LCD-160
Manual

for descriptions of the applicable soft keys.

STATUS LED INDICATORS

Power (green) illuminates when AC power is within normal

operating limits.
Fire Alarm (red) illuminates when at least one fire alarm event

exists. It will flash if any of these events are unacknowledged.
Pre-Alarm (red) illuminates when at least one pre-alarm event

exists. It will flash if any of these events are unacknowledged.
Security (blue) illuminates when at least one security event

exists. It will flash if any of these events are unacknowledged.
Supervisory (yellow) illuminates when at least one supervi-

sory event exists. It will flash if any of these events are unac-

knowledged.
System Trouble (yellow) illuminates when at least one trou-

ble event exists. It will flash if any of these events are unac-

knowledged.
Other Event (yellow) (future release).