dn-3404:b • 11/17/09 — Page 1 of 2

UZC-256

Universal Zone Coder
Software Release 2.0

Annunciator Control Systems

dn-3404:b • D-140

General

The UZC-256 Universal Zone Coder enables the Notifier intel-

ligent fire alam control panels (FACPs), network control annun-

ciators (NCAs) and compatible legacy systems to provide

positive non-interfering successive zone coded outputs. Up to

256 separate codes may be programmed to operate on the

three coded outputs. Each output is used to code or pulse up

to 3 Amps of Notification Appliance power.

Features

• Coded output from the UZC-256 can be fed to multiple out-

put circuits.

• Up to 256 individually programmed codes.
• Three 3-Amp outputs.
• Programmable rounds of code (1 to 99 rounds).
• Up to four digits per round.
• Up to 15 pulses per digit of code.
• Optional general alarm.
• Programmable code and round(s) delay.
• Programmable pulse and digit pause times.
• Connects and communicates over panel EIA-485 interface.
• Programmable for California code.
• Weight 1.75 lbs.

Release 2.0 Features

• Secondary UZC use: counting alarm operation activates

UZC relays after specified number of alarms.

• Programmable address EIA-485 range (1-32).
• No code/counting selection for non-fire points.

Applications

The UZC-256 provides three outputs that supply unique coded

information to certain output circuits, depending on the alarm

initiation condition. This can be useful when employing coded

outputs in floor-above, floor-below applications, or to provide

various numbers of rounds for bell circuits and strobe or lamp

circuits.

NOTE: Due to the nature of coded outputs, the UZC-256 is not
compatible with notification devices which do not produce a steady
or non-periodic sound. Periodic appliances that produce their own
code (such as some codes available with electronic sounders) will
not be compatible with the UZC-256. Refer to the UZC-256 Instal-
lation Manual for a list of compatible panels.

Construction & Operation

The UZC-256 provides three coded output relays, each rated

for three amps at 30 VDC. These relays are controlled by a

predefined program, and can be set to respond to general

alarm conditions with the fire alarm system.
The UZC-256 and the CPU use the EIA-485 circuit for commu-

nication. When installed, the zone coder has a programmable

address on the EIA-485 interface.
Assignment of points to zone codes within the UZC-25 is pro-

grammable in the NFS2-3030, NFS2-640, NFS-320 and NCA-

2 (see programming manuals for details).

Electrical Specifications

Standby current: 35 mA.
Alarm current: 55 mA.

Installation

Locate the system, including components and peripheral

equipment in the following nominal environment:
Temperature: 60° to 80°F (15.6° to 26.7°C).
Relative humidity: 40% to 60% (non-condensing).

Agency Listings and Approvals

In some cases, certain modules or applications may not be

listed by certain approval agencies, or listing may be in pro-

cess. Consult factory for latest listing status.

UL Listed: S624

ULC Listed: CS118/CS733/CBP696

MEA: 289-91-E Vol. III; 290-91-E Vol. III; 291-91-E Vol. II;

17-96-E; 345-02-E; 232-06-E

CSFM: 7165-0028:141; 7165-0028:144; 7165-0028:157;

7165-0028:181; 7165-0028:214 (NFS-640); 7165-0028:224

(NFS-3030); 7170-0028:153; 7170-0028:154; 7170-

0028:182; 7170-0028:216 (NFS-640); 7170-0028:223

(NFS-3030, NFS2-3030), 7165-0028:243 (NFS2-640)

FDNY: COA #

Lloyd’s Register: 93/60/40 (E2) (AM2020/AFP1010)

FM Approved

UZC-256 Universal Zone Coder

0704u