Notifier APS-6R User Manual

Aps-6r, 0 amp auxilary power supply, General

Advertising
background image

DN-5952:A1 • 08/20/09 — Page 1 of 2

APS-6R

6.0 Amp Auxilary Power Supply

Power Supplies

DN-5952:A1 • E-121

GENERAL

The APS-6R is a state-of-the-art, 150 watt, switching auxiliary

power supply providing 24 VDC of filtered DC power. The

APS-6R provides two 24 VDC output circuits, each rated for

3.0 Amps in alarm and 2.0 Amps continuous. It is used for the

operation of peripheral audible/visual devices (alarm signaling

appliances) for the NOTIFIER AM2020, AFP1010, NFS-3030,

NFS-640, AFP-400, AFP-300, AFP-200, System 5000, and

System 500 control panels.

FEATURES

• Lightweight, compact design.
• “Off-line” switching technology.
• Forward topology.
• Unique design — magnetic flux-sensed converter elimi-

nates need for opto-coupler feedback.

• 120 or 240 VAC (@ 50/60 Hz) field-selectable.
• Wide input voltage range: 90 – 132 VAC, 180 – 264 VAC.
• High efficiency.
• Output circuits with overload protection.
• Built-in “brown-out” circuitry.
• Diagnostic trouble LED.
• Plug-in connector for in cabinet applications and screw ter-

minals for remote device applications.

• Shares battery and charger circuit with control panel.
• Power-limited design, per UL requirements.
• Surface-mount technology conserves panel space.
• AC Fail supervision with field-selectable delay per UL 864.
• Heavy-duty clamp-type terminals accept up to 12 AWG (3.1

mm²) wire.

CONSTRUCTION AND OPERATION

When used with the CAB-3 or CAB-4 Series (CAB-A3/-A4, -

B3/-B4, -C3/-C4, or -D3/-D4), the APS-6R mounts to a CHS-4

or CHS-4L mounting chassis. If more than one APS-6R is nec-

essary to satisfy Audible/Visual (DC) power requirements, con-

nect additional APS-6R power supplies together as described

in the Installation Instruction Manual. When used with the

AFP-200, the APS-6R mounts in the lower portion of the cabi-

net where batteries would normally mount (BB-17 required).

When used with the System 500, only one APS-6R may be

mounted in the right-most position in the cabinet.
Underwriters Laboratories requires that all Signaling Appli-

ances be approved for use with the selected control system

due to voltage operating range criteria. Use only those appli-

ances listed for use with the associated control system. Refer
to Device Compatibility Document #15378.

SPECIFICATIONS

Compatible with: AM2020, AFP1010, NFS-3030, NFS-640,

AFC-600, AFP-400, AFP-300, AFP-200, System 5000, and

System 500 control panels.

DIMENSIONS:

6.125" (15.558 cm.) high x 4.25" (11.43 cm.) wide x 3.0" (7.62

cm.) deep at protruding edge, 2.25" (5.715 cm.) deep at box

edge on opposite side.

ELECTRICAL SPECIFICATIONS

AC primary input power (TB1): 120 VAC: 120 VAC, 60 Hz,

2.5 A. 240 VAC (cut JP1): 240 VAC, 50 Hz, 1.2 A.
DC secondary input power (TB3): TB3-1 (+), TB3-2 (–).
24 VDC output power (TB2): Total 6.0 A (4.0 A continuous).

Circuit 1 (TB2-1, TB2-2; or J1): 3.0 A @ 24 VDC power-lim-

ited.

Circuit 2 (TB2-3, TB2-4; or J2): 3.0 A @ 24 VDC power-

limited.
Fuses: F1 (AC supervision): 250 VAC, 4.0 A, 3 AG. F2

(battery supervision): 32 VAC, 10.0 A, 3 AG.
Trouble supervision bus: J3 output: Form-A contact (open

collector).

J4 input: Form-A contact (open collector).

NOTE: J3 and J4 can be interchanged.

Loss of AC indication: Immediate indication (default); 8-

hour delay (cut JP2); 16-hour delay (cut JP2 and JP3).

MECHANICAL SPECIFICATIONS

The APS-6R in its enclosure measures approximately 6"

(15.24 cm) x 4" (10.16 cm) x 3” (7.62cm).

CABINETS FOR MOUNTING

CAB-3/CAB-4 Series: Use CHS-4 and CHS-4L chassis, for

AM2020, AFP1010, NFS-3030, NFS-640, AFP-400, AFP-300,

and System 5000 control panels.
System 500: Can mount one APS-6R if the face module

expansion card (such as an ICE-4) is not installed.