Panel capabilities, Alarmnet, Installation requirements – Notifier IPGSM-COM User Manual

Page 2: Electrical specifications, Cabinet specifications, Shipping specifications, Temperature and humidity ranges, Product line information, Agency listings and approvals

Advertising
background image

Page 2 of 2 — DN-60656:B1 • 02/23/2011

NOTIFIER® is a registered trademark of Honeywell International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Primary Central Station ID (two digits) obtained from your
monitoring station.

Primary Subscriber ID (four digits) obtained from your mon-
itoring station.

Communication Module's MAC ID, and MAC CRC number
located on outside of box, and inside of the module.

All of these parameters are assigned by the monitoring station.

See

IPGSM-COM Installation and Setup Guide for full details.

NOTE: Some assembly is required.

Panel Capabilities

The IPGSM-COM communicator panel is compatible with fire
panels that use the Contact ID communications format as
described in the SIA DC-05 standard. Any NOTIFIER fire
alarm control panel with a Contact ID-capable DACT meets
that standard — including ONYX series panels wtih UDACT,
FireWarden series panels, 411 series panels, SFP-5UD/10UD,
and NSP25.

AlarmNet

Honeywell's AlarmNet has been the nationwide leader in
alarm communications technology since 1986. A reliable alter-
native for the transmission of alarm signals, our radio network
provides extensive coverage in the United States and Canada

AlarmNet Network Control center processes signals from pow-
erful servers in multiple locations equipped with 24/7 infra-
structure support. The AlarmNet network consist of redundant
hardware servers, hot back-up databases and generators with
battery back-up at all locations to ensure continuity of service.
Signals from AlarmNet are transmitted to the central station's
receivers using multiple communications paths consisting of
the Internet, radio network or toll-free POTS service.

Installation Requirements

UL COMPLIANCE

To meet UL864/NFPA compliance, ensure the following:

IPGSM-COM must be mounted within the same room and
within 20 feet of host Fire Alarm Control Panel sounder, or
other remote sounder.

IPGSM-COM must be powered from the same un-switched
facility power source branch as the host Fire Alarm Control
Panel.

IPGSM-COM must use the 7AH battery to provide 24-hour
backup capability.

Electrical Specifications

Transformer:
Primary: 120 VAC, 60 Hz, 0.50 A.

Secondary: 18VDC, 50 VA.

Current Requirements:
PowerBoost1 power supply: 90mA Standby, 90 mA Active

iGSM Communications Module: 80mA Standby, 500mA

Active (peak during transmission)

Dialer Capture Module: 40mA Standby, 85mA Active

LED Display board: 10mA Standby, 10mA Active

TOTAL: 220mA Standby, 685mA Active

Battery: One 12 V 7.0 AH lead-acid battery (not supplied).
(IPGSM-COM cabinet holds one 7.0 AH battery.)

Cabinet Specifications

Dimensions: 14.875" H x 12.75" W x 3.0" D (37.8 cm H x
32.4 cm W x 7.6 cm D)

Color: Red

Shipping Specifications

Weight: 5.3 lbs. (6.94 kg)

Dimensions: 15.625" H x 13.79" W x 9.25" D (39.7 cm H x
34.9 cm W x 23.9 cm D)

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.

Product Line Information

IPGSM-COM: Internet and Digital Cellular Fire Communicator
Panel. Includes red cabinet with key, wall outlet box, Dialer
Capture Module, iGSM Communications Module, antenna and
mounting adapter, PowerBoost1 power supply, LED display
board, transformer, manual, and required screws, cables, etc.

GSM-ANT3DB: 3db gain external/remote antenna

7626-50HC: 50 ft. antenna cable, low loss

7626-25HC: 25 ft. antenna cable, low loss

WA7626-CA: SNA to N Adapter

7720P: IPGSM-COM handheld programmer

HPTCOVER: Plug in transformer box for IPGSM communicator

BAT-1270: Battery 12 Volts, 7 AH, sealed

Agency Listings and Approvals

The listings and approvals below apply to the basic IPGSM-
COM
communicator panel. In some cases, certain modules
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.

UL: S789

CSFM: 7300-1645:0183

Advertising