411 Series

Slave Digital Alarm
Communicator Transmitters

Miscellaneous

DN-6619:A2 • K-95

General

The 411 Series DACTs are compact, multifaceted, slave Digi-

tal Alarm Communicator Transmitters designed for a variety of

fire, security, and non-fire applications. The series features the

411 and 411UD, which provide three and four monitoring

channels (inputs) respectively. These slave DACTs are a solu-

tion for applications that require an existing (or new) fire alarm

control panel (FACP) to transmit system status to an off-site

monitoring facility for Central or Remote Station compliance.

Due to extremely flexible programming options, the 411 Series

slave DACTs are also ideal for monitoring non-fire and security

control panels. With fifteen selectable transmission formats

(including ADEMCO Contact ID) compatibility with virtually all

Digital Alarm Communicator Receivers (DACR) is ensured.

Programming can be accomplished on-site with a hand-held

programmer (PRO-411), or remotely (411UD only) using the

PK-411UD programming utility. This Windows®-based remote

upload/download software package permits system interroga-

tion and revision from a remote site.

Features

• Three (411) or four (411UD) monitoring channels (inputs).
• Inputs may be individually programmed to monitor the host

control panel for:
Fire Alarm.
Fire Trouble.
Fire Supervisory.
Process Monitoring.
AC Power Loss.
Security Alarm.
Other (Fire and Non-Fire Events).

• Fully supervised trigger inputs require a contact closure for

activation.

• 12- or 24-VDC operation, jumper-selectable.
• Industry-first, UL recognized, “dialer-runaway” prevention

feature.

• Dual-line, rotary or touch-tone-dial DACT interfaces to pub-

lic switched telephone network (leased phone lines are not

required).

• Includes 15 reporting formats, including the popular

ADEMCO Contact ID format.

• Capable of transmitting the following DACT information, in

addition to vital system status of the host control panel:
DACT troubles.
Telephone line 1 and 2 voltage fault.
Primary or Secondary Central Station communication

fault.

System off-normal.
24-hour normal test.
24-hour abnormal test.

• Long-distance Carrier Access Code (CAC) compliant,

accepting up to 20-digit Central Station telephone numbers.

• Fully programmable transmittal codes for fire, security, pro-

cess monitoring, and others.

• Field-programmable with PRO-411 hand-held programmer.

• Programmable from remote site with optional PK-411UD

programming software (model 411UD only).

• View 411 Series status offsite in real time, with optional PK-

411UD programming software, without ever compromising

monitoring protection at the protected premises (model

411UD only).

• Programming sequence based on NOTIFIER’s popular

SFP-1024 Control/Communicators.

• Integral piezo sounder (both models) with local silence

switch (model 411UD only).

• One Form-C relay, fully programmable (model 411UD only).
• Complies with NFPA 72 (Central Station and Remote Sta-

tion [DACT only - not polarity reversal] Fire Alarm Systems).

• Surface Mount Technology (SMT).
• Extremely compact enclosure, measuring only 6.75"

(17.145 cm) W x 4.40" (11.176 cm) H x 1.05" (2.667 cm) D.

• Shares identical footprint with 911 Series for replacement

purposes.

Host Panel Compatibility

Host panels must include AC Fail Delay option to meet NFPA

Central Station Requirements. Panels with this feature include

RP-1001, RP-1002, RP-2001, RP-2002, System 500, System

5000, AFP-200, AFP-300, AFP-400, NFS-320, NFS-640,

NFS2-640, AFP1010, AM2020, NFS-3030, and NFS2-3030.

Housing

The 411 Series DACTs are fully enclosed in a compact hous-

ing measuring only 6.75" (17.145 cm) W x 4.40" (11.176 cm) H

x 1.05" (2.667 cm) D. The housing enclosure consists of an

aluminum backbox painted red with a matching cover secured

by two captive screws. The overlay includes large areas to

independently mark programming options for the three or four

channels (inputs), relay, and also includes printed terminal and

diagnostic LED designations. The overall compact size of the

enclosure permits mounting of these DACTs in virtually any

control panel’s enclosure, or alternately, adjacent to the host

control panel.

Phone Line Connections

Two modular phone connections on the 411 Series are acces-

sible with the cover in place and provide connections for two