Notifier FCPS-24S8 User Manual

& 8-amp 24-volt remote power supplies, General, Features

Advertising
background image

dn-6927:a • 04/30/09 — Page 1 of 2

FCPS-24S6(C/E) & FCPS-
24S8(C/E)

6- & 8-Amp 24-Volt
Remote Power Supplies

Power Supplies

dn-6927:a

General

The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are

remote power supplies with battery charger. The FCPS-24S6/-

24S8 may be connected to any 12 or 24 volt fire alarm control

panel (FACP) or may be used as stand-alone supplies. Pri-

mary applications include notification appliance (bell) circuit

(NAC) expansion (to support ADA requirements and NAC syn-

chronization) or auxiliary power to support 24 volt system

accessories. The FCPS-24S6/-24S8 provides regulated and

filtered 24 VDC power to four notification appliance circuits

configured as either four Class B (Style Y) or Class A (Style Z,

with ZNAC-4 option module). Alternately, the four outputs may

be configured as all non-resettable, all resettable or two non-

resettable and two resettable. The FCPS-24S6/-24S8 also

contains a battery charger capable of charging up to 18 AH

batteries. FCPS-24S6C & FCPS-24S8C are ULC-listed.

NOTE: Unless otherwise specified, the terms FCPS-24S6 and
FCPS-24S8 used in this document refers to the standard FCPS-
24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the
FCPS-24S6E and FCPS-24S8E

Features

• UL-Listed NAC synchronization using System Sensor,

Wheelock, or Gentex “Commander

2

” appliances.

• Operates as a “sync-follower” or as a “sync-generator”

(default). See note on page 2.

• Contains two fully-isolated input/control circuits - triggered

from FACP NAC (NAC expander mode) or jumped perma-

nently “ON” (stand-alone mode).

• Four Class B (Style Y) or four Class A (Style Z, with

ZNAC-4 module) NACs.

• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load out-

put, with 3 amps maximum/circuit, in NAC expander mode

(UL 864).

• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous

output in stand-alone mode (UL 1481).

• Compatible with coded inputs; signals passed through.
• Optional power-supervision relay (EOLR-1).
• In stand-alone mode, output power circuits may be config-

ured as: resettable, (reset line from FACP required),

non-resettable, or a mix of two and two.

• Fully regulated and filtered power output - optimal for pow-

ering four-wire smoke detectors, annunciators, and other

system peripherals requiring regulated/filtered power.

• Power-limiting technology meets UL power-limiting require-

ments.

• Form-C normally-closed trouble relay.
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
• AC trouble report selectable for immediate 2-hour delay.
• Works with virtually any UL 864 fire alarm control which uti-

lizes an industry-standard reverse-polarity notification cir-

cuit (including unfiltered and unregulated bell power).

• Requires input trigger voltage of 9 - 32 VDC.
• Self-contained in compact, locking cabinet - 15”H x 14.5”W

x 2.75”D (cm: 38.1H x 36.83W x 6.985D).

• Includes integral battery charger capable of charging up to

18 AH batteries. Cabinet capable of housing 7.0 AH batter-

ies.

• Battery charger may be disabled via DIP switch for applica-

tions requiring larger batteries.

• Fixed, clamp-type terminal blocks accommodate up to 12

AWG (3.1mm

2

) wire.

Specifications

Primary (AC) Power:
• FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum.
• FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum.
• Wire Size: minimum #14 AWG (2.0mm

2

) with 600 V insula-

tion.

Control Input Circuit:

Trigger Input Voltage: 9 to 32 VDC.

Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9

- 16 V).

Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA

maximum.
Output Circuits:
• +24 VDC filtered, regulated.
• 3.0 A maximum for any one circuit.
• Total continuous current for all outputs (stand-alone mode):

FCPS-24S6: 4.0 A maximum.
FCPS-24S8: 6.0 A maximum.

• Total short-term current for all outputs (NAC expander mode):

FCPS-24S6: 6.0 A maximum.
FCPS-24S8: 8.0 A maximum.

Secondary Power (Battery) Charging Circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 VDC.

6927pho1.jpg