DN-7047:F • 12/20/2013 — Page 1 of 4

NCA-2

ONYX

®

Series

Network Control Annunciator

Network Systems

DN-7047:F • A0-126

7047

pho1

.jpg

NCA-2 in ABS-2D backbox

General

The NOTIFIER NCA-2 is a second-generation Network Con-
trol Annunciator for the

NOTI•FIRE•NET™ network, com-

patible for use with ONYX® Series nodes such as the NFS2-
3030, NFS-3030, NFS-320, NFS-640 and NFS2-640 fire
alarm control panels, as well as first-generation NCA Net-
work Control Annunciators. Additionally, the NCA-2 may be
configured with DVC Series products to create one or more
Digital Audio Command Centers on NOTI•FIRE•NET™. The
NCA-2 provides system control and display capabilities for
all, or for selected network nodes.

The NCA-2 display consists of a 640-character backlit LCD
display, and a control interface consisting of “soft” keys used
to navigate screen menus, “hard” keys with fixed control func-
tions, and a QWERTY keypad.

When connected to one or more networked panels the
NCA-2 provides network control and status/history display
capabilities. It may also be configured as the Primary Display
for displayless nodes on the network.

Hardware Features

• Certified for seismic applications when used with the

appropriate seismic mounting kit.

• Approved for Marine applications when a marine-listed

version is used with marine-listed compatible equipment.
See DN-60688.

• Full supervision of all inputs and network integrity.

• Enhanced-format 640-character LCD display with back-

lighting.

• ACS bus for LED or graphic annunciators (EIA-485).

• Optically isolated printer interface (EIA-232).

• 11 LED status indicators: Power, Controls Active, Fire

Alarm, Pre-Alarm, Security, Alert, Supervisory, Trouble,
Signal, Silence, CPU Failure, Point Disabled, Other Event.

• Alphanumeric QWERTY rubber keypad.

• Four status relays: Alarm, Trouble, Supervisory, Security

(Form-C).

• Nonvolatile real-time clock can be synchronized with net-

work by master node.

• Optional Security Keyswitch enables keypad functions.

• Optional Security Tamper switch.

• Supports up to 32 remote ACS annunciators and mod-

ules.

• Requires 24 VDC, and a network connection.

• RDP port for LCD-160 or terminal mode LCD2-80.

NOTE: NCA-2 Firmware version 14.0 (and higher) can support
LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not
both at the same time.

Function Features

• Individual Enable/Disable or Group Enable/Disable local

for networked ONYX series panels.

• Control ON/OFF networked ONYX series panel control

points.

• Read Status networked ONYX series panel points and

zones.

• Network paging control/HVAC control .

• Network-wide: Acknowledge, Silence, Reset.

• Lamp Test (local to NCA-2).

• History Buffer (1000 Alarm events; 4000 System events).

• Print NCA-2 programming and history reports.

• Report status of networked panels and their respective

field devices to a central station via a single UDACT-2 (see
data
sheet DN-60686).

• One Master level, nine User level passwords. The Master

can assign each User access levels (programming, alter
status).

• Interactive Summary Event Count display, event handling

package.

• Online programming and alter-status programs.

• Intuitive user guidance program including interactive soft

keys.

• Enhanced Read Status/Alter Status displays.

• New history filters for report displaying and printing: All

Events, Only Alarms, Only Troubles, Only Supervisory,
Only, Security, Time Interval, Point Range.

• Fully programmable node-mapping subsystem.

• Advanced/Basic Walk-Test program.

• Timer control for Auto Silence, AC Fail Delay.

• Meets Canadian ULC display requirements.

• Environmental adjustment controls to maximize LCD legi-

bility.

• Meets NFPA requirements for Firefighter Smoke Control

Station (FSCS) and HVAC.