Technical summary – Notifier Vulcain 90DM4 User Manual

Page 3

Advertising
background image

Technical summary

General Specifications

Use

Wall or duct mountable CO

2

detector for industrial or commercial use

Size

13.7 x 9.5 x 4.4 cm (15.4 x 3.75 x 1.75 in.)

Weight

SM: 200 g (8.8 oz.)

DT: 300 g (10.56 oz.)

Power Requirement

17-27 Vac or 24-38 Vdc, 200 mA @ 24Vac

Detection Range

0-2000 ppm, 0-5%

Accuracy

+/- 100 ppm + 3% of reading

Response Time

< 60 sec. (for 90% of the reading)

Sensor Life Expectancy >

10

years

Relay Output Rating

5A, 30 Vdc or 250 Vac (resistive load)

Display LCD

(optional)

Optional Outputs

4-20 mA (current sourcing only)

1 SPDT Relay

Operating Humidity

0-95% RH, Non-condensing

Range

Operating Temperature

0 °C to 40 °C (32 °F to 100 °F)

Range

Warranty 5

Years

(limited)

Ratings and Certifications

Certified to

CAN/CSA C22.2 No. 61010-1

116662

Conforms to ANSI/UL

61010-1