PAGE 4

23 MAR 2003

MAN0504-02

OCX404



2.3

Analog Input / Output

OCX Back View Connector – Shows

corresponding I/O pin location

*




*

±10V LOAD

±20mA LOAD/RECEIVER

±10V SOURCE

±10V SOURCE

±20mA SELF POWERED TRANSMITTER

LOOP POWERED TRANSMITTER

+

+

20mA LOOP POWER

I1

C

I2

C

I3

C

I4

C

Q1

C

Q2

C





Signal

Pin

OCX404 Analog In / Out

I1 Input

1

C Common

I2 Input

2

C Common

I3 Input

3

C Common

I4 Input

4

C Common

I5 Input

5

C Common

I6 Input

6

C Common










001OCX005


Note: The Voltage/Current mode switch is located directly

above each input. Moving a switch towards Pin 1* selects
±20mA for the corresponding channel. Moving the switch
towards Pin 12 selects

±10VDC. Each channel must be set

up in Cscape for the desired mode in addition to the physical
switch settings for proper signal scaling in the PLC registers.








3 INTERNAL

SCHEMATIC


Mini Digital Input

C

iI1

I/O Connector

To

Controller

VCC

Field

Side







I/O Connector

Mini Digital Output


VC

Q

V+

From

Controller




Field

Side







Specification for transient voltage suppressors used on digital output circuitry is 33V, 300W.