Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Fillter
Constant) on module response to a temperature change.

5

ANALOG INPUT CONVERSION FACTOR


The following table describes how real-world inputs are scaled into the controller. Given a known input
current, the data value is configured by using the conversion factor from the table. The following formula
is used: Data = Input Current (mA) / Conversion Factor

Example:

The user selects a current range of ±20mA:


1.

The known input current is 14mA.

2.

Using the table, the conversion factor for the current range of ±20mA is 0.000625.

3.

To determine the data value, the formula is used:

Data = Input Current (mA) / Conversion Factor
22400 = 14mA / 0.000625

Conversion of Real-World Inputs into Controller

Selected Range

Input

Register Data

Conversion Factor

+20.00 32000

0.00 0

±20mA

-20.00 -32000

0.000625


+10.00 32000

0.00 0

±10 V

-10.00 -32000

0.0003125