23 MAY 2003

PAGE 7

OCX404

6

ANALOG CONVERSION OUTPUT FACTOR


The following table describes how program data values are scaled to real-world analog voltage outputs by
the module. Given a desired output current, the data value is converted by using the conversion factor
from the table. The following formula is used: Data = Output Current (mA) / Conversion Factor

Example:

The user selects a current range of ±20mA:


1.

The desired output current is 12mA.

2.

Using the table, the conversion factor for the current range of ±20 mA is 0.000625.

3.

To determine the data value, the formula is used:

Data = Output Current (mA) / Conversion Factor
19200 = 12mA / 0.000625

Conversion of Real-World Outputs into Controller

Selected Range

Output

Register Data

Conversion Factor

+20.00 3200

0.00 0

0 to +20mA

-20.00 -32000

0.000625

+10.00 32000

0.00 0

±10 V

-10.00 -32000

0.0003125

7

DIGITAL INPUT / OUTPUT CHARACTERISTICS


7.1 Digital

Input

Digital Input Chart



.125(

±15%) V-A




0

35VDC



7.2

Digital Output

Derating Chart



0 10 20 30 40 50 60

°C

32 50 68 86 104 122 140

°F

0

AMPS / CHANNEL

.5


.4

.3


.2


.1




Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.