Interface pinouts – Avocent Cyclades PM IPDU User Manual

Page 48

Advertising
background image

38 Cyclades PM IPDU Installer/Administrator/User Guide

Interface Pinouts

Table A.2: PM42 IPDU Specifications

Characteristics

Electrical

Input Voltage

Three phases, phase to phase 208 VAC

Max Input Current

24A

Max Output Current Total

16A on any single bank (XY, YZ or XZ)

-or-

13.8A evenly distributed on each bank (XY, YZ or XZ)

NOTE: Maximum allowed current in any bank is limited to 16A
although the maximum of 24A input current per phase must not be
exceeded. If equal loads are provided to all banks then, in order to
have this maximum input current of 24A, the maximum allowed
current per bank will have to be decreased to 13.8A.

Max Output Current Each Outlet

42 - IEC320-C13: 12A at 208 VAC (42 places)

Environmental

Operating Temperature

0-50ºC

Mechanical

Weight

10.89 kg

Physical Dimensions (W x D x H)

2.2 x 2.5 x 72.0 in

Table A.3: Pinouts for IN and OUT RS-232 Serial Ports

Signal

Name/Function

I/O

IN Pin

OUT Pin

RTS

Request to Send

(O)

5

1

DTR

Data Terminal Ready

(O)

7

2

TxD

Transmit Data

(O)

6

3

Gnd

Ground

N/A

4

4

CTS

Clear to Send

(I)

1

5

RxD

Receive Data

(I)

3

6

DCD

Data Carrier Detect

(I)

2

7

Advertising