Wiring specifications – American Power Conversion RT XLI/XLICH User Manual

Page 14

Advertising
background image

10

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Wiring Specifications

Adhere to national and local electrical codes when wiring.

* Terminal screw tightening torque: 40 lbf-in (4.5 N-m)
The acceptable input frequency range is 40 to 70 Hz.
The output frequency is user selectable. Refer to the PowerView display menu screens for available options.

Input Connections

Output Connections

Main Input

Single-Phase: Wire to L1, N, and

Three-Phase: Wire to L1, L2, L3, N, and

Hardwire

Single-Phase: Wire to L1, N, and

Three-Phase: Wire to L1, L2, L3, N, and

Bypass Input (optional)

Single-Phase: Wire to B1, N, and

Three-Phase: Wire to B1, B2, B3, N, and

Single-phase PDU

XL battery pack PDU to UPS: Wire L1, N,

System

Wiring

Number

of Phases

Voltage

Current

Full Load

(maximum

External Input

Circuit Breaker

(typical)

Wire Size

(typical)*

SURT15000XLI/

XLICH

Input

1

220/230/

240 Vac

83 A

100 A / 1-pole

25/35 mm

2

(2/1 AWG)

Input

3

380/400/

415 Vac

28 A / phase

35 A / 3-pole

6 mm

2

(8 AWG)

Output

1

220/230/

240 Vac

65 A

not required

25 mm

2

(2 AWG)

Output

3

380/400/

415 Vac

22 A / phase

not required

6 mm

2

(8 AWG)

SURT20000XLI/

XLICH

Input

1

220/230/

240 Vac

105 A

125 A / 1-pole

35/50 mm

2

(1/0 AWG)

Input

3

380/400/

415 Vac

35 A / phase

50 A / 3-pole

10 mm

2

(6 AWG)

Output

1

220/230/

240 Vac

87 A

not required

35 mm

2

(1 AWG)

Output

3

380/400/

415 Vac

29 A / phase

not required

10 mm

2

(6 AWG)