American Power Conversion RT XLI/XLICH User Manual

Page 29

Advertising
background image

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

25

General

Fault

Need Bat Replacement.

One or more battery pairs are in need

of replacement.

Refer to battery installation

procedure.

No Batteries Are

Connected.

No battery power is available.

Check that batteries are installed and

connected properly.

Discharged Battery.

The UPS is on battery operation and

the battery charge is low.

Shut down the system and the load

or restore the incoming voltage.

Low- Battery.

The UPS is on battery operation and

the battery charge is low.

Weak Batt(s) Detected.
Reduced Runtime.

One or more weak battery pairs

detected (only applicable for internal

battery modules).

Replace the weak battery pairs.

Batt Temperature Exceeded

Upper Limit.

The temperature of one or more

battery packs has exceeded system

specifications.

Contact APC Customer Support.

Refer to Contact Information in this

manual.

Battery Over-Voltage

Warning.

The battery voltage is too high and the

charger has been deactivated.

Runtime Is Below Alarm

Threshold.

The predicted runtime is lower than

the user-specified minimum runtime

alarm threshold. Either the battery

capacity has decreased, or the load has

increased.

Option 1) Allow the batteries to

recharge.
Option 2) If possible, increase the

number of battery modules.
Option 3) Reduce the load.
Option 4) Decrease the alarm

threshold.

Condition

PowerView Display

Message

Reason for Message

Corrective Action

Advertising