Field charging example – Comfort-Aire A-VFH42PA-1 User Manual

Page 22

Advertising
background image

22

VFH InverterFlex

®

- Outdoor Ductless Mini-Split

Heat Controller

Field Charging Example

36KBTU/H

Outdoor Unit

Four 9KBTU/H

Indoor Units

OUTDOOR UNIT

INDOOR UNIT

LINE SET/LENGTH

36KBTU/H

j

9KBTU/H

a / 30 ft (9m)

k

9KBTU/H

b / 35 ft (10.6m)

l

9KBTU/H

c / 40 ft (12.2m)

m

9KBTU/H

c / 50 ft (15.2m)

The allowable line length for a 36KBTU/H unit is

131 ft (40m) as shown on the table on page 17.

The total line set length for the example installation

is 154 ft (47m) which is greater than the allowable

length, so additional refrigerant is required.

To calculate the additional refrigerant needed ,

multiply the additional line length by .024 oz/ft

(20g/m) for a 36KBTU/H unit. To get the additional

line length, subtract the allowable line length from

the total system line length.

Total length of refrigerant line set = a + b + c + d

= 30' (9m)+ 35' (10.6m) + 40’ (12.2m) + 49' (15.2m)
=

154 ft (47m) total

CALCULATION EXAMPLE:

Total system line length 154 ft (47m) minus the

allowable line length 131 ft (40m) = 23 ft (7m)

To determine the additional refrigerant, the additional

line length 23 ft (7m) is multiplied by 0.24 oz/ft

(20g/m) = 5.5 oz (154g)

In this example, 5.5 oz (156g) of additional refrigerant

is needed for a complete charge.