Inverter Series System Introduction:

System Selection:

The total capacity of

ALL the indoor units can not

exceed 150% of the capacity of the outdoor unit.

However, we recommend sizing the indoor unit’s

total capacity to be less than or equal to 100% of

the outdoor unit’s capacity. If sized beyond 100% of

the outdoor unit’s capacity, when all the indoor units

receive a call for cooling/heating, the entire system

will still only be able to achieve the rated capacity. of

the outdoor unit The inverter compressor can run at

a higher frequency but may not provide full capacity

to all indoor units. Sizing above 100% is usually done

because one or more indoor units may not be in use

the majority of the time.
Additionally, the total capacity of all indoor units cannot

be less than 50% of the outdoor unit’s capacity.

System Application:

This system is not designed to be a sole source of

heat for a home/building. While the units can operate

in low ambient conditions, they cannot provide the full

rated capacity for heat at low outdoor temperatures. An

additional heat source may be required in areas such

as the northern USA and Canada during the winter.
This system must be run in modes that do not conflict.

For example, one indoor unit cannot be run in cool

mode and another indoor unit in heat mode. All indoor

units modes must be harmonized for the system to

properly operate. The fan mode can run in conjunction

with any other mode, while the cooling mode can be

run in conjunction with the dehumidification mode.

However all other modes must match among the

indoor units.

Heat Exchanger

Liquid Receiver

Four Way Valve

Oil Separator

Gas/Liquid Separator

Indoor Unit

Outdoor Unit

Electronic

Expansion Valve

Stop

Valve

Capillary

Compressor

Heat Exchanger

Heat Exchanger

Heat Exchanger

Heat Exchanger

Heat Exchanger

Heating

Cooling

System Schematic

NOTE: The number of indoor units may vary depending on the capacity of the outdoor unit. This is an

example of a five (5) zone system.