WIKA safety manual temperature transmitter T32.xS

11583631.03 08/2014 GB/D/F/E

Application (see page 12):

Example 1

Sensor type Pt100, configured measuring range = -50 … +100 °C, so configured

measuring span = 150 K.

This is not smaller than 84 K. Thus the total safety accuracy is 2 % FS,

so 2 % * 150 K = 3 K, or 2 % * 16 mA = 320 μA in terms of the current output

Example 2

Sensor type Pt100, configured measuring range = 0 … 50 °C, so configured

measuring span = 50 K

This is smaller than 84 K, thus the total safety accuracy is 2 K,

thus 2 K / 50 K = 4 %, and 4 % * 16 mA = 640 μA in terms of the current output

2.7 Configuration changes

WARNING!

During the configuration change, the safety function is not active! Safe

operation is only admissible with activated write protection (password).

Carry out configuration changes within the permissible specifications in accordance

with chapter 2.1 “Intended use in safety applications”.

With the supplied configuration tools, such items as the write protection for model

T32.xS can be set:

Configuration software WIKA_T32

AMS

SIMATIC PDM

DTM in conjunction with operating software to the FDT/DTM Standard, e.g.

PACTware, FieldMate

HART

®

hand-held terminal FC475, FC375, MFC4150

WARNING!

The safety function must be checked by testing following any configuration

procedure.