WIKA safety manual temperature transmitter T32.xS

Appendix: SIL declaration of conformity

SIL Declaration of Conformity

Functional safety per IEC 61508:2010 / IEC 61511:2004

Page 4/4

3.7 FMEDA duplex sensor

thermocouple with internal

cold junction (safety function

for 4 … 20 mA output)

T32.xS

stand

alone

T32.xS with duplex sensor thermocouple

(internal cold junction)

Close coupled

1)

Extension wire

2)

Low stress

3)

High stress

4)

Low stress

3)

High stress

4)

λ

DU

[FIT]

5)

11

21

411

211

4.011

λ

DD

[FIT]

5)

76

266

3.676

3.876

36.076

λ

SU

SD

[FIT]

5)

76

76

76

76

76

SFF Sensor/Transmitter

6)

- / 93,4 % 95,0 / 93,4 % 90,0 / 93,4 % 95,0 / 93,4 % 90,0 / 93,4 %

PFD

avg

for T

proof

1 year

7)

4,70 * 10

-5

9,08 * 10

-5

1,80 * 10

-3

9,23 * 10

-4

1,76 * 10

-2

DC diagnostic coverage

99,0 %

-

-

-

-

1) Close coupled: The temperature transmitter is located in the connection head of the electrical thermometer.

2) Extension wire: The temperature transmitter is located outside of the connection head of the electrical thermometer, for

example in a cabinet distant from the measuring point

3) Low stress applies to a low vibration environment or the use of a cushioned sensor. Operation below 67 % maximum rating

according to specification

4) High stress applies to a high vibration environment. Operation above 67 % maximum rating according to specification

5) FIT = Failure in time, Unit: Quantity of failures per 10

9

h

6) Green marked values: SFF sufficient for SIL 2

7) Green marked values: PFD

avg

< 35 % of the maximum allowed value for SIL 2 (PFD

avg

< 0,0035)

Yellow marked values: PFD

avg

< maximum allowed value for SIL 2 (PFD

avg

< 0,01)