WIKA safety manual temperature transmitter T32.xS

3.1 FMEDA Pt100 4-wire

(safety function for

4 … 20 mA output)

T32.xS

stand

alone

T32.xS with Pt100 4-wire

Close coupled

1)

Extension wire

2)

Low stress

3)

High stress

4)

Low stress

3)

High stress

4)

λ

DU

[FIT]

5)

10

16

150

130

1.410

λ

DD

[FIT]

5)

75

119

935

955

8.675

λ

SU

SD

[FIT]

5)

76

76

76

76

76

SFF Sensor/Transmitter

6)

- / 93,6 % 88,0 / 93,6 % 86,0 / 93,6 % 88,0 / 93,6 % 86,0 / 93,6 %

PFD

avg

for T

proof

1 year

7)

4,52 * 10

-5

7,15 * 10

-5

6,58 * 10

-4

5,71 * 10

-4

6,18 * 10

-3

DC diagnostic coverage

99,0 %

-

-

-

-

3.2 FMEDA Pt100 3-wire

(safety function for

4 … 20 mA output)

T32.xS

stand

alone

T32.xS with Pt100 3-wire

Close coupled

1)

Extension wire

2)

Low stress

3)

High stress

4)

Low stress

3)

High stress

4)

λ

DU

[FIT]

5)

10

19

200

183

1.910

λ

DD

[FIT]

5)

74

113

836

861

7.674

λ

SU

SD

[FIT]

5)

76

76

76

76

76

SFF Sensor/Transmitter

6)

- / 93,8 % 81,3 / 93,8 % 80,0 / 93,8 % 82,0 / 93,8 % 80,0 / 93,8 %

PFD

avg

for T

proof

1 year

7)

4,38 * 10

-5

8,32 * 10

-5

8,76 * 10

-4

8,01 * 10

-4

8,37 * 10

-3

DC diagnostic coverage

99,0 %

-

-

-

-

3.3 FMEDA Pt100 2-wire

(safety function for

4 … 20 mA output)

T32.xS

stand

alone

T32.xS with Pt100 2-wire

Close coupled

1)

Extension wire

2)

Low stress

3)

High stress

4)

Low stress

3)

High stress

4)

λ

DU

[FIT]

5)

10

19

200

183

1.910

λ

DD

[FIT]

5)

73

112

835

860

7.673

λ

SU

SD

[FIT]

5)

76

76

76

76

76

SFF Sensor/Transmitter

6)

- / 93,8 % 82,0 / 93,8 % 80,0 / 93,8 % 82,0 / 93,8 % 80,0 / 93,8 %

PFD

avg

for T

proof

1 year

7)

4,33 * 10

-5

8,12 * 10

-5

8,76 * 10

-4

8,01 * 10

-4

8,37 * 10

-3

DC diagnostic coverage

99,0 %

-

-

-

-

Page 2/4

Appendix: SIL declaration of conformity

SIL Declaration of Conformity

Functional safety per IEC 61508:2010 / IEC 61511:2004

1) Close coupled: The temperature transmitter is located in the connection head of the electrical thermometer.

2) Extension wire: The temperature transmitter is located outside of the connection head of the electrical thermometer, for

example in a cabinet distant from the measuring point

3) Low stress applies to a low vibration environment or the use of a cushioned sensor. Operation below 67 % maximum rating

according to specification

4) High stress applies to a high vibration environment. Operation above 67 % maximum rating according to specification

5) FIT = Failure in time, Unit: Quantity of failures per 10

9

h

6) Green marked values: SFF sufficient for SIL 2

7) Green marked values: PFD

avg

< 35 % of the maximum allowed value for SIL 2 (PFD

avg

< 0,0035)

Yellow marked values: PFD

avg

< maximum allowed value for SIL 2 (PFD

avg

< 0,01)