3. Specifications

Response time

T05 < 5 s (per DIN EN 60751)

T09 < 10 s (per DIN EN 60751)
Maximum working pressure

150 bar

3.5 Accuracy
Analogue signal

≤ ± 0,5 % of span
Switching output

≤ ± 0.8 % of span

Display

≤ ± 0.8 % of span ± 1 digit
Temperature sensor

± (0.15 K + 0.002 | t |)

| t | is the value of the temperature in °C without consideration of the sign.

The actually achievable accuracy is significantly determined by the mounting situation (immersion

depth, sensor length, operating conditions). This is especially the case for large temperature gradients

between the environment and the medium.

3.6 Reference conditions

Temperature:

15 ... 25 °C

Atmospheric pressure: 950 ... 1,050 mbar

Humidity:

45 ... 75 % relative

Nominal position:

Process connection lower mount

Power supply:

DC 24 V

Load:

see "Output signal"