Faults, Error code description, Problem possible cause measure – WIKA TSD-30 User Manual

Page 23

Advertising
background image

23

WIKA operating instructions temperature switch model TSD-30

GB

11613025.02 12/2011 GB/D/F/E

8. Faults

Error code Description

ATT1

On changing the switch point, the system automatically reduces the reset point

ATT3

Password entered for menu access is incorrect

ERR

Internal error

OL

Measuring range exceeded > approx. 5 % (display blinks)

UL

Below measuring range < approx. 5 % (display blinks)

Acknowledgement of an error display by pressing the "Enter" key.

Problem

Possible cause

Measure

No output signal

Cable break

Check the through drilling

No output signal / line break

Mechanical load too high

Replace sensor with a suitable design

No output signal

No/wrong power supply

Rectify the power supply

No/wrong output signal

Wiring error

Observe the pin assignment

Wrong output signal

Process temperature out of range;

Sensor drift caused by overtemperature

Sensor burnout/short circuit

Check temperature range

Send the instrument to the manu-

facturer

Wrong output signal

Sensor drift caused by chemical attack

Check media compatibility

Wrong output signal and too long

response time

Wrong mounting geometry, for example

mounting depth too deep or heat dissi-

pation too high
Deposit on the sensor

Move the temperature-sensitive area

of the sensor into the medium

Remove deposit

Signal span too small

Power supply too high/low

Rectify the power supply

Signal span drops

Humidity has entered

Assemble the cable correctly

If complaint is unjustified, we will charge you the complaint processing fees.