WIKA operating instructions temperature switch model TSD-30

GB

11613025.02 12/2011 GB/D/F/E

6. Commissioning, operation

6.4 Parameters

Parameter Description

SP1/SP2

Hysteresis function: Switch point switching output (1 or 2)

FH1/FH2

Window function: Window high switching output (1 or 2)

RP1/RP2

Hysteresis function: Reset point switching output (1 or 2)

FL1/FL2

Window function: Window low switch output (1 or 2)

EF

Extended programming functions

RES

Return the set parameter to the factory settings

DS1/DS2

Switch delay time, which must occur without interruption before any electrical signal change occurs

(SP1 or SP2)

DR1/DR2

Switch delay time, which must occur without interruption before any electrical signal change occurs

(RP1 or RP2)

OU1

Switching function switching output (1 or 2)

OU2

HNO = hysteresis function, normally open

HNC = hysteresis function, normally closed

FNO = window function, normally open

FNC = window function, normally closed

UNIT

Changing units

(If the measuring range is outside the indication range, a unit switching is not possible and the UNIT

parameter is not indicated)

SETR

Measuring range scaling (analogue output)

“4 mA” or “0 V” determines at which temperature the output signal is to be 4 mA or 0 V.

“20 mA” or “10 V” determines at which temperature the output signal is to be 20 mA or 10 V.

OFS

Offset adjustment (3 % of span)

DISM

Display value in display mode

ACT = Actual temperature value; LOW, HIGH = Minimum, Maximum temperature value

OFF = display off;

SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,

SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2

DISR

Rotate display indicator by 180°

RHL

Clear the Min- and Max-value memories

PAS

Password input, 0000 = no password; Password input digit by digit

TAG

Input of a 16-figure alphanumeric measuring point number