WIKA operating instructions expansion thermometer, model 70

WARNING!

Before storing the instrument (following operation), remove any residual

media. This is of particular importance if the medium is hazardous to health,

e.g. caustic, toxic, carcinogenic, radioactive, etc.

6. Commissioning, operation

Please observe the following general requirements when mounting and operating the

instrument:

„

The scale range of the temperature control instrument should be selected so that the

maximum temperature present at the sensor does not exceed the scale range. Once

the switch point is exceeded, you should also be careful of any temperature rise that

occurs.

„

In operation, the instrument should not be exposed to any strong vibrations or shock

loadings.

„

Avoid soiling and strong fluctuations of the ambient temperature.

„

Cutting the measuring line leads to the destruction of the instrument and, thus, to a

shut-down of the electrical output signal.

Electrical connection

The terminal connections are given on the product label which is located

around the edge of the housing.

6.1 Installation conditions

Before mounting the sensor, check whether the sensor material used (specified in the

delivery note) is chemically resistant/neutral to the medium being measured. This also

applies to thermowells.

Make sure that the suitable accessories required for fastening the case of the instrument

into the panel are available.

The accessories are either fitted or located in a bag fastened to the thermometer.

„

If possible, the entire length of the stem should be exposed to the temperature being

measured. However, at least the length of the active part that corresponds to the length

of the expansion vessel (active length).

„

In pipelines or other measuring points, the temperature sensor must be positioned as

far towards the flow as possible.

„

When using thermowells, it must be ensured that the stem does not touch the bottom of

the thermowell.