8. Commisioning, operation / 9. Contact protection ...

8.4 Adjusting the set pointers
The setting of the set points is achieved using the adjustment lock in the

window with the aid of the adjustment key (part of the scope of delivery;

found in standard instruments on the side of the terminal box).

The set pointers for the limit switches are freely adjustable over the full

scale range. For reasons of switching accuracy, switching reliability and

service life of the mechanical measuring systems, the switch points

should be between 10 % and 90 % of the measuring span.

Commissioning
During the commissioning process pressure surges must be avoided at

all costs. Open the shut-off valves slowly.

9. Contact protection measures

Mechanical contacts must not exceed the specified electrical values for

switching current and switching voltage independent of each other, not

even for a short time only.

For capacitive or inductive loads we recommend one of the following

protective circuits: