WIKA operating instructions magnetic snap-action contact model 821

GB

16

2003325.03 03/2011 GB/D/F/E

9. Contact protection measures

9.1. Inductive load with DC voltage

With DC voltage the contact protection can be achieved via a free-

wheeling diode, connected in parallel to the load. The polarity of the

diode must be arranged so that it closes when the operating voltage is

on.

Example:

Contact protection

measure with free-

wheeling diode

Contact

Diode

Contact

Contact

9.2. Inductive load with AC voltage

With AC voltage two protection measures are possible:

Example:

Contact protec-

tion measure with

voltage-depend-

ent resistor VDR

Example:

Contact protection

measure with RC

element