Operating instructions digital indicator di15 – WIKA DI15 User Manual

Page 19

Advertising
background image

Operating Instructions Digital Indicator DI15

V1.3

02/2011

- 19 -

- When pressing button 1 again, the device will display “1.dEL“ (delay of output 1).

- Use button 2 and button 3 to set the desired value [in sec.] for the switching-delay of output 1.

- Press button 1 to validate the selection. The display shows “1.dEL“ again.

- When pressing button 1 again, the device will display “1.out“ (type of output 1).

- Use button 2 or button 3 (middle resp. right button) to select the desired output function.

Display

Kind of output

Note

nPn

Low-Side

NPN, open collector,

switching GND

PnP

High-Side

PNP, open collector,

switching +Ub

Pu.Pu

Push-Pull

- Press button 1 to validate the selection. The display shows “ 1.out“ again.

- When pressing button 1 again, the device will display “1.Err“ (preferred state of output 1).

- Use button 2 and button 3 (middle resp. right button) to set the desired initial state in case of an error.

Display

Preferred state of the output

Note

off

Inactive in case of an error

Low-/High-side-switch is opened in case of an
error.
Push-Pull-output is low in case of an error.

on

Active in case of an error

Low-/High-side-switch is closed in case of an
error.
Push-Pull-output is high in case of an error.

- Press button 1 to validate the selection. The display shows “1.Err“ again.

- In case you selected a 3-point-controller you have to make the following settings similar to the settings

you already made for output 1:
2.dEL“ (delay of output 2), “2.out“ (kind of output 2), “2.Err“ (preferred state of output 2).

- When pressing button 1 again, (only if you configured the device with min-/max-alarm)

the device will be displaying “A.out“ (kind of the alarm-output).

- Use button 2 or button 3 (middle resp. right button) to select the desired kind of the alarm-output.

Display

Kind of the alarm-output

Note

nPn

Low-Side

NPN, open collector,

switching GND

Switching output is closed (connected to
GND) as long there is no alarm-condition, and
is opened if there is an alarm-condition.

PnP

High-Side

PNP, open collector,

switching +Ub

Switching output is closed (is under voltage)
as long there is no alarm-condition, and is
opened if there is an alarm-condition.

Pu.Pu

Push-Pull

Switching output is high with no alarm-
condition and changes to low if there is an
alarm-condition.

Please Note:

The switching outputs are inverted when using them as alarm-outputs!

This means as long there is no alarm-condition, the switching output will be
active! In case of an alarm-condition the output will become inactive!

Note:

When using the output function “min-/max-alarm, individual “ the setting for type of alarm
output is used for both alarm-outputs.

- Press button 1 to validate the selection. The display shows “ A.out“ again.