9. Error codes

When detecting an operating state which is not permissible, the device will display an error code

The following error codes are defined:


Error presumed

cause Solution

Err 1

- Input signal to high

- The input sighnal must be within

- Exceeding of the measuring

- Sensor broken

the limits

range

- Sensor shorted

- Check sensor, transducer / transmitter

- Check device configuration

- Reset the counter

Err 2

- Input signal to low /negative

- The input sighnal must be within

- Values below measuring

- Current below 4 mA

the limits

range

- Sensor shorted

- Check sensor, transducer/ transmitter

- Sensor broken

- Check device configuration

- Counter underflow

- Reset the counter

Err 3

- Incorrect scale

- The error message will be reset if the

- Display range has been

- Counter overflow

display value is below 9999

exceeded

Err 4

- Incorrect scale

- The error message will be reset if the

- Values below display range

- Counter underflow

display value is above -1999

- Defective device

- Reset the counter

Err 7

- Valid operation temperature

- Stay within valid temperature range

- System error

has been exceeded

- Exchange the defective device

Err 9

- Sensor broken /shorted

(PT100)

- Check sensor

- Sensor defective

-Sensor broken (Thermocouple)

Err 11

- Incorrect scale

- Check settings and input signal

- Value could not be calculated