Document 2.4.54 Revision 0

July 2006

Small Power Substation Transformers

14

High-Voltage Bushings

High-voltage bushings are typically shipped installed in

the unit. If the bushings were removed for shipment,

install the bushings per the manufacturer’s guidelines.

!

WARNING: DO NOT EXCEED THE

CANTILEVER LOAD RATING OF THE

BUSHING. GREATER LOADS MAY CAUSE BUSHING

DAMAGE THAT COULD RESULT IN SEVERE

PERSONAL INJURY, DEATH, OR PROPERTY

DAMAGE.

Draw-lead bushings usually require no maintenance

except as described on page 15. Maintenance

instructions for condenser-type bushings are furnished

with the bushings.

Low-Voltage Bushings

Low-voltage bushings are typically shipped installed in

the unit. If the bushings were removed for shipment,

install the bushings per the manufacturer’s guidelines.

Surge Arresters

Transformers may be furnished with optional

distribution class, intermediate class, or station

class surge arresters. Intermediate and station class

arresters are shipped separately from the transformer

to prevent damage. Upon delivery, unpack the arresters

and carefully inspect them for damage, especially the

porcelain components. Install surge arresters according

to the instructions found on page 9.

Radiators

Transformers are furnished with radiator assemblies

(usually panel type) to dissipate heat from the

transformer. Cooling fans may also be furnished

to provide additional loading capability without

overheating the transformer. Radiator assemblies may

be shipped separately from the transformer to reduce

the shipping size of the transformer and to prevent

damage. When radiators are shipped unattached,

they should be installed in the field according to the

instructions on page 8.