I/o data, No. bytes, Notes – Norgren VP51 DeviceNet Installation Instructions User Manual

Page 6: Devicenet interface details, Devicenet parameters

Advertising
background image

6


6. DEVICENET INTERFACE DETAILS


I/O Data

Name I/O

Type

(see Note 1)

No.

Bytes

Format

Demand Pressure

Polled Output

2

12 bit integer (0 to 4095)
0 = minimum (zero) pressure
4095 = full scale output + 5% span
(see Note 2)

Actual Pressure

Polled Input

2

12 bit integer (0 to 4095)
0 = minimum (zero) pressure
4095 = full scale output + 5% span
(see Note 3)

Status Byte

Polled Input

1

Bit 0: Set if difference between Demand
Pressure
and Actual Pressure exceeds Error
Limit
(see parameter 10).
Bit 1: Set if Bit 0 has been set for longer
than Error Delay (see parameter 11).
Bit 2: Set if Actual Pressure

Threshold A

(see parameter 12).
Bit 3: Set if Actual Pressure

Threshold B

(see parameter 13).
Bits 4-7: Not used.
(See Note 3)

Notes

:

1) Inputs and Outputs are defined from the perspective of the DeviceNet network.
2) For 150 psi variant Demand Pressure value= 26 x (Required Pressure in psi), e.g. to output 100 psi, set

Demand Pressure value to 2600.
For 10 bar variant Demand Pressure value = 390 x (Required Pressure in bar), e.g. to output 6 bar, set
Demand Pressure value to 2340.
IMPORTANT - Only 12 of the 16 bits in the two Demand Pressure bytes are used. The four most
significant bits are ignored. Setting the Demand Pressure value above 4095 or below 0 may lead
to unpredicted output pressures.

3) If the polled input is read as a single value of 3 or more bytes, the two least significant bytes hold the

actual pressure and the third least significant is the status byte. For example, a returned value of
266044 (0x040F3C) represents an actual pressure of 0x0F3C = 3900 = 100% full scale and a status
byte of 0x04 = bit 2 set.

DeviceNet Parameters


The following parameters are available via a DeviceNet configuration tool (e.g. RSNetworx) or via DeviceNet
explicit messaging, using the class, instance, attribute and byte length details in the table. To use a DeviceNet
configuration tool, it is necessary to register the DeviceNet VP51 EDS file on the configuration tool. The EDS file
can be downloaded from

www.odva.org

.

Parameter

No.

Name Format

Default
Value

Class
Id

Instance
Id

Attribute
Id

Byte
length

1

Baud Rate

Selectable from:
Autobaud, 125Kb/s, 250Kb/s,
500Kb/s (see note 1)

Autobaud 3

1

2

1

2 Serial

number

Read only 4 byte integer

Factory
set

1 1

6

4

3 Demand

Pressure

Read only integer, 0-4095
0 = minimum (zero) pressure
4095 = full scale output + 5%
span
(same as polled output, see
note 2)

- 3

1 114

(0x72)

2