Switching capacity, Recommended circuit, Switching function – Norgren 18D Pressure Switch Datasheets User Manual

Page 3

Advertising
background image

Our policy is one of continued research and development. We therefore reserve the right to amend,

without notice, the specifications given in this document. © 2013 Norgren GmbH

12/13

1998-5249c

N/en 5.11.001.03

18D

Switching capacity

Commutator with gold plated contacts

Current

type

Load type

*2)

U min

[V]

Max. permanent current Imax [A] at U *1)

(UL & CSA)

M 12x1 DIN EN 175301-803, form A

30 V 30 V 48 V 125 V 250 V

Contact life

AC

ohmic, inductive

6

0,1

0,1

0,1

0,1

0,1

≥ 2 x 10

5

switching cycles

DC

ohmic, inductive

6

0,1

—

—

—

—

Reference number: 20/min, Reference temperature: +20°C.

I min = 1 mA at 24 V DC or 5 mA at 6 V DC

*1) Higher currents (5 A max) will cause a reduction of the durability of the micro-switch contacts. Futhermore additional measuements has to be taken to

fulfil the EMV regulation 2004/108/EG by the manufacturer

*2) Spark quenching/overload protection will be necessary using inductive loads.

Recommended circuit

Spark quenching and EMV intrinsically safe

1. Quick diode (D) with tv

≤

200 ns, parallel to inductive load.

2. RC link in parallel to load in parallel to switching contact.

Dimensioning principles:

R

L

in W

≈

0,2 x RLoad in W

C in [µF]

≈

ILoad in [A]

+

-

p

D

1)

2)

R

C

R

L

U

DC (AC)

d.c (a.c.)

~

~

2

3

1

p

2

4

1

p

Switching function

Plug DIN EN 175301-803, form A

Microswitch SPDT

Terminals 1 - 3: Contacts close

on rising pressure.

Terminals 1 - 2: Contacts open

on rising pressure.

Switching function

IEC 947-5-2, M12 x 1:

Microswitch SPDT

Terminals 1 - 4: Contacts close

on rising pressure.

Terminals 1 - 2: Contacts open

on rising pressure.

R

L

= Load resistance