Warning – Burnham MPC User Manual
Page 14
 
1
Table V: Minimum Installation Clearances To
 Combustible Materials (Inches) per
 UL76 (Packaged / Firetested Boiler)
C
A
B
Chimney
D
E
F
Boiler Above
Front
Connector
Rear
Sides
Below
MPC
18
48
18
18
18
NC *
* NC - Noncombustible Flooring
Note: See Table III for recommended service clearance 
 to access rear of boiler.
NOTE	1:		Listed	clearances	comply	with	UL	726,	Standard	
for	Oil-Fired	Boiler	Assemblies.
NOTE	2:		MPC	Series	boilers	can	be	installed	in	rooms	
with	clearances	from	combustible	material	as	listed	above.		
Listed	clearances	cannot	be	reduced	for	alcove	or	closet	
installations.
WARNING
All boiler builds, except boilers bearing the 
UL Label, are suitable for installation on 
combustible floor. Do not install boiler on 
carpeting.
Floor construction should have adequate 
load bearing characteristics to bear the 
weight of the boiler filled with water (see 
Table 1). A boiler foundation similar to the 
one shown in Figure  is recommended if 
the boiler room floor is weak or uneven or if 
a water condition exists.
4. PROVIDE AIR SUPPLY AND VENTILATION to
accommodate proper combustion.
WARNING
Failure to supply adequate air to the boiler will 
result in unsafe boiler operation.
For	commercial	and	industrial	equipment,	permanent	
facilities	for	supplying	an	ample	amount	of	outside	air	
shall	be	provided	in	accordance	with	the	following.
For	boiler	rooms	adjacent	to	outside	walls,	and	where	
combustion	air	is	provided	by	natural	ventilation	from	
the	outside,	there	shall	be	a	permanent	air	supply	inlet	
having	a	total	free	area	of	not	less	than	1	sq.	in.	per	
4,000	Btu	per	hr.	(35	sq.	in.	per	gal.	per	hr.)	(5.5	cm2	
per	kw.)	of	total	input	rating	of	the	burner	or	burners	
and	in	no	case	less	than	35	sq.	in.	(0.425	m2).
For	boiler	rooms	not	adjacent	to	outside	walls,	the	
combustion	air	shall	be	supplied	in	a	manner	acceptable	
to	the	authority	having	jurisdiction.
Figure : Boiler Foundation
3. PROVIDE ADEQUATE FOUNDATION for the
unit. Refer to Figure 2.