Notice – Burnham MPC User Manual
Page 64
 
6
c.
BOiLER PiPiNG, DOMEsTic hOT WATER
(DhW) APPLicATiON	–	The	MPC	boiler	can	be	
used	in	many	different	piping	applications	to	produce	
Domestic	Hot	Water	(DHW).		In	some	applications,	
depending	on	the	control	strategy	(outdoor	reset,	
setpoint	operation,	etc.)	and	size	of	the	boiler,	it	is	
recommended	to	isolate	the	space	heating	load	from	the	
DHW	load.		For	example,	if	the	domestic	load	is	more	
than the space heating load, it is beneficial to dedicate 
one	or	more	boilers	solely	to	DHW	production	and	one	
or	more	boilers	solely	to	space	heating,	since	during	
mild	weather	conditions,	the	boiler(s)	will	have	more	
capacity	than	is	required.		Piped	in	the	recommended	
manner,	the	space	heating	boiler(s)	can	be	shut	down	
during	the	summer	months	to	conserve	energy	and	to	
avoid	short	cycling.
The	use	of	indirect	water	heaters	for	domestic	
hot	water	generation	is	commonly	recommended	
since	they	provide	DHW	storage.		A	tempering	
valve	and	recirculation	loop	are	advantageous	in	
these	applications,	because	they	provide	both	high	
temperature	and	tempered	domestic	water	to	the	
Figure 5: Discharge Piping for Pressure Relief Valve
system,	eliminating	the	need	to	purge	and	waste	water	
until	it	reaches	the	desired	temperature.		See	Figures	
49a,	49b,	50a	and	50b	for	recommended	indirect	water	
heater	piping.
NOTICE
DO NOT use the boiler circulator as an indirect 
domestic hot water system circulator.
D.
RELiEf vALvE DischARGE PiPiNG, see
Figure 54. Pipe discharge to within 4” of floor or to a 
suitable	drain.		Do	not	reduce	piping	size	or	install	shut-
off	valve	in	discharge	piping.
If	discharge	is	weeping,	do	not	plug	relief	valve	or	cap	
discharge	piping,	replace	valve	immediately.
E.
iNsTALL ELEcTRic WiRiNG in	accordance	
with	National	Electric	Code	and	local	regulations.		A	
separate	ELECTRICAL	CIRCUIT	should	be	run	from	
meter	with	a	Fused	Disconnect	Switch	in	this	Circuit.
NOTICE
When possible, domestic hot water production should utilize dedicated boiler(s). This will allow the other 
boiler(s) to be shut down and isolated during the summer months. If the boiler load is shared between 
heating and domestic hot water, then one needs to determine if a hot water priority is required. If a priority 
is not selected, erratic domestic hot water production may result during the beginning and end of every 
heating season. Conversely, a priority for domestic hot water production may cause a significant heating
zone activation delay, in an improperly balanced system. Parallel piping conversions may require isolation
from the heating system to prevent system flow influence on DHW performance. Consult a qualified system 
heating professional to design for the proper application.