E. INSPECT COMBUSTION CHAMBER TARGET

WALL AND LINER, AND SWING DOOR

GASKET.

1. Open burner swing door using procedure previously

outlined in Paragraph D of this section.

2. Using a fl ashlight, inspect the rear target wall and

liner. The target wall should be rigidly secured to
the rear boiler section. The combustion chamber
liner should be evenly distributed in the boiler
chamber. If either is damaged, they must be

replaced.

3. Inspect ceramic rope located on the swing door.

The rope must be evenly distributed around the

perimeter of the door groove and cannot bunch or
overhang. There must not be a gap where the two
ends of the rope meet. Repair or replace if the rope
is damaged or if there is a gap between the ends.

F. INSPECT NOZZLE AND ELECTRODES /

CHANGE FIRING RATE FOR BECKETT
BURNERS.
Refer to Section II, Paragraph J, No. 7,

steps b through o for nozzle installation, electrode and
head setting inspection.

Steam Boilers Only

Packaged V83 - V86 steam boilers are shipped with

the lower (standard) fi ring rate nozzle installed.

Packaged V87 - V89 boilers are provided with one

nozzle, installed in the burner, that provides the
same fi ring rate as the water boiler of the same size.

Inspect the installed nozzle and assure that the

nozzle is the correct size and type as specifi ed in

Table 6 of this manual.

Inspect and measure burner electrodes. Refer to

Figure 27 of this manual for the proper electrode
settings.

Close the burner swing door and securely seal the

door to the boiler front section by reinstalling the
hardware and securing the door using procedure
previously outlined in Paragraph D of this section.

Water Boilers Only

Packaged V8 water boilers are shipped with the

higher input oil nozzle installed in the burner.

A second oil nozzle for the lower (minimum) fi ring

rate is shipped loose for the V83 - V86 models,
attached to the burner. Select the proper oil
nozzle for the installation. The lower (minimum)
input nozzle will provide greater boiler effi ciency.
However, boiler output will be reduced. Refer to

Table 1B for ratings. If the higher rate is desired,

inspect the installed nozzle and assure that the
nozzle is the correct size and type as specifi ed in

Table 6 of this manual.

If the lower (minimum) input is desired, remove

the nozzle which was factory installed. Locate the
lower (minimum) fi ring rate nozzle that is supplied
loose. Confi rm the nozzle is the proper size and
type for the lower fi ring rate as specifi ed in Table

6 of this manual. Install the proper nozzle in the

burner nozzle adaptor.

G. INSPECT NOZZLE AND ELECTRODES

/ CHANGE FIRING RATE FOR CARLIN

102CRD BURNERS. Refer to Section II, Paragraph

K, No. 7, steps b through d for nozzle installation,
electrode and head setting inspection.

Follow instructions in Paragraphs A through E.

Steam or Water Boilers

Packaged V87 - V89 steam boilers are provided
with one nozzle, installed in the burner, that

provides the same fi ring rate as the water boiler of
the same size.

Inspect the installed nozzle and assure that the

nozzle is the correct size and type as specifi ed in

Table 6 of this manual.

H. INSPECT NOZZLE AND ELECTRODES /

CHANGE FIRING RATE FOR CARLIN ELITE
EZ BURNERS.
Refer to Section II, Paragraph L, No.

7, steps a through c for nozzle installation, electrode

and head setting inspection.

Follow instructions in Section III, Paragraphs A through

E.

Steam Boilers Only

Packaged V83 - V86 steam boilers are shipped with

the lower (standard) fi ring rate nozzle installed.
Packaged V87 - V89 boilers are provided with one
nozzle, installed in the burner, that provides the
same fi ring rate as the water boiler of the same size.

Inspect the installed nozzle and assure that the

nozzle is the correct size and type as specifi ed in

Table 6.

Water Boilers Only

Packaged V8 water boilers are shipped with the

higher input oil nozzle installed in the burner.

A second oil nozzle for the lower (minimum) fi ring

rate is shipped loose for the V83 - V86 models,
attached to the burner. Select the proper oil
nozzle for the installation. The lower (minimum)
input nozzle will provide greater boiler effi ciency.
However, boiler output will be reduced. Refer
to Table 1B For fi ring rates. If the higher rate is
desired, inspect the installed nozzle and assure that
the nozzle is the correct size and type as specifi ed in

Table 6.