Burnham V8 Series User Manual

Page 31

Advertising
background image

31

A.

EVALUATE THE EXISTING WATER SYSTEM.

Design a piping system and install boiler which will
prevent oxygen contamination of boiler water and
frequent water additions.

1. There are many possible causes of oxygen

contamination such as:

a. Addition of excessive make-up water as a result

of system leaks.

b. Absorption through open tanks and fi ttings.

c. Oxygen permeable materials in the distribution

system.

2. In order to insure long product life, oxygen sources

must be eliminated. This can be accomplished by
taking the following measures:

a. Repairing system leaks to eliminate the need for

addition of make-up water.

b. Eliminating open tanks from the system.

c. Eliminating and/or repairing fi ttings which allow

oxygen absorption.

d. Use of non-permeable materials in the

distribution system.

e. Isolating the boiler from the system water by

installing a heat exchanger.

G

N

I

N

R

A

W

t

s

u

m

g

n

i

p

i

p

n

r

u

t

e

r

d

n

a

y

l

p

p

u

s

m

e

t

s

y

S

.

e

p

i

p

r

e

l

i

o

b

t

c

e

r

r

o

c

o

t

d

e

t

c

e

n

n

o

c

e

b

e

h

t

g

n

i

z

i

s

s

d

n

e

m

m

o

c

e

r

m

a

h

n

r

u

B

t

n

e

i

c

i

f

f

u

s

y

l

p

p

u

s

o

t

r

o

t

a

l

u

c

r

i

c

m

e

t

s

y

s

e

r

u

t

a

r

e

p

m

e

t

F

°

0

2

a

w

o

l

l

a

o

t

)

M

P

G

(

w

o

l

f

g

n

i

z

i

s

n

e

h

W

.

m

e

t

s

y

s

e

h

t

n

i

l

a

i

t

n

e

r

e

f

f

i

d

e

r

u

s

s

e

r

p

e

h

t

,

r

o

t

a

l

u

c

r

i

c

m

e

t

s

y

s

e

h

t

d

n

a

d

r

a

o

b

e

s

a

b

,

s

r

o

t

a

i

d

a

r

l

l

a

f

o

p

o

r

d

g

n

i

t

c

e

n

n

o

c

l

l

a

d

n

a

g

n

i

b

u

t

t

n

a

i

d

a

r

.

d

e

r

e

d

i

s

n

o

c

e

b

t

s

u

m

g

n

i

p

i

p

N

O

I

T

U

A

C

m

o

r

f

e

c

n

a

r

a

e

l

c

h

c

n

i

½

m

u

m

i

n

i

m

n

i

a

t

n

i

a

M

.

s

l

a

i

r

e

t

a

m

e

l

b

i

t

s

u

b

m

o

c

o

t

g

n

i

p

i

p

r

e

t

a

w

t

o

h

B. CONNECT SYSTEM SUPPLY AND RETURN

PIPING TO BOILER. See Figures 13A, 13B and
13C. Also, consult I=B=R Installation and Piping
Guides.

1. If this boiler is used in connection with refrigeration

systems, the boiler must be installed so that the
chilled medium is piped in parallel with the heating
boiler using appropriate valves to prevent the chilled
medium from entering the boiler. See Figure 12.
Also, consult I=B=R Installation and Piping Guides.

2. If this boiler is connected to heating coils located

in air handling units where they may be exposed
to refrigerated air, the boiler piping must be
equipped with fl ow control valves to prevent gravity
circulation of boiler water during the operation of
the cooling system.

3. If boiler is used with an Alliance™ Indirect-Fired

Domestic Water Heater, install the Alliance™ as
a separate heating zone. Refer to the Alliance™
Installation, Operating, and Service Instructions for
additional information.

4. Use a boiler bypass if the boiler is to be operated

in a system which has a large volume or excessive
radiation where low boiler water temperatures may
be encountered (i.e. converted gravity circulation
system, etc.) The bypass should be the same size as
the supply and return lines with valves located in the
bypass and return line as illustrated in Figures 13A,
13B and 13C in order to regulate water fl ow for
maintenance of higher boiler water temperature.

G

N

I

N

R

A

W

e

l

i

h

w

,

e

c

i

v

e

d

f

f

o

-

t

u

c

r

e

t

a

w

w

o

l

a

f

o

e

s

u

e

h

T

w

o

l

e

b

s

i

l

e

v

e

l

n

o

i

t

a

i

d

a

r

s

s

e

l

n

u

d

e

r

i

u

q

e

r

t

o

n

.

d

e

d

n

e

m

m

o

c

e

r

y

l

h

g

i

h

s

i

,

r

e

l

i

o

b

e

h

t

If a low water cut-off is required, it must be
mounted in the system piping above the boiler. The
minimum safe water level of a hot water boiler is
just above the highest water containing cavity of
the boiler; that is, a hot water boiler must be full of
water to operate safely.

5. If it is required to perform a long term pressure

test of the hydronic system, the boiler should fi rst
be isolated to avoid a pressure loss due to the escape
of air trapped must fi rst be removed from the boiler.

SECTION IV: WATER BOILER PIPING AND TRIM

E

C

I

T

O

N

e

n

i

l

r

e

t

a

w

,

e

s

i

o

n

m

e

t

s

y

s

e

v

i

s

s

e

c

x

e

n

i

t

l

u

s

e

r

y

a

m

l

a

u

n

a

m

s

i

h

t

n

i

d

e

i

f

i

c

e

p

s

s

a

r

e

l

i

o

b

e

p

i

p

o

t

e

r

u

l

i

a

F

.

r

e

v

o

y

r

r

a

c

r

e

t

a

w

d

n

a

s

n

o

i

t

a

u

t

c

u

l

f

Advertising