Burnham V8 Series User Manual

Page 69

Advertising
background image

69

Carlin Elite EZ Burners

a. Carlin EZ-1HP and EZ-2HP burners use a head

positioning bar to fi x the head setting based
on nozzle size. To adjust this setting, bar must
be changed to the next larger or smaller bar
available. Refer to Section II, Paragraph D for
details.

4. READJUST THE TURBULATOR SETTING only

if necessary.

Riello

Burners

a. V82 through V89

Move the turbulator setting forward or back one
position at a time to optimize the smoke and
CO2 readings.

b. Turn “OFF” burner and remove Riello

Combination Pressure Gauge and Bleeder Valve
Assembly. Install pressure port/bleeder plug and
tighten. Start burner again.

5. TURN “OFF” BURNER and remove pressure

gauge. Install gauge port/bleeder plug and tighten.
Start burner again.

G

N

I

N

R

A

W

s

g

n

i

t

t

i

f

e

n

i

l

l

i

o

y

n

a

e

v

o

m

e

r

r

o

n

e

s

o

o

l

t

o

n

o

D

.

g

n

i

t

a

r

e

p

o

s

i

r

e

n

r

u

b

e

l

i

h

w

6. FLAME FAILURE

The V8 boiler controls operate the burner
automatically. If for unknown reasons the burner
ceases to fi re and the reset button on the primary
control has tripped, the burner has experienced
ignition failure.

G

N

I

N

R

A

W

n

e

h

w

r

e

n

r

u

b

e

h

t

t

r

a

t

s

o

t

t

p

m

e

t

t

a

t

o

n

o

D

t

i

n

u

e

h

t

n

e

h

w

,

d

e

t

a

l

u

m

u

c

c

a

s

a

h

l

i

o

s

s

e

c

x

e

n

o

i

t

s

u

b

m

o

c

e

h

t

n

e

h

w

r

o

,

r

o

p

a

v

f

o

l

l

u

f

s

i

.

t

o

h

y

r

e

v

s

i

r

e

b

m

a

h

c

H. CHECK FOR CLEAN CUT OFF OF

BURNER.

1. AIR IN THE OIL LINE between fuel unit and

nozzle will compress when burner is on and will
expand when burner stops, causing oil to squirt from
nozzle at low pressure as burner slows down and
causing nozzle to drip after burner stops. Usually
cycling the burner operation about 5 to 10 times will
rid oil line of this air.

2. IF NOZZLE CONTINUES TO DRIP, repeat

Paragraph I, No. 1. If this does not stop the
dripping, remove cut-off valve and seat, and wipe
both with a clean cloth until clean, then replace
and readjust oil pressure. If dripping or after burn
persist replace fuel pump.

Figure 28: R7184 Terminals, LED and Reset Button

I.

TEST CONTROLS.

1. Check thermostat operation. Raise and lower

thermostat setting as required to start and stop
burner.

G

N

I

N

R

A

W

d

e

r

e

d

i

s

n

o

c

s

i

r

e

l

i

o

b

e

h

t

f

o

n

o

i

t

a

l

l

a

t

s

n

i

e

r

o

f

e

B

s

l

o

r

t

n

o

c

r

e

l

i

o

b

l

l

a

f

o

n

o

i

t

a

r

e

p

o

e

h

t

,

e

t

e

l

p

m

o

c

y

r

a

m

i

r

p

e

h

t

y

l

r

a

l

u

c

i

t

r

a

p

,

d

e

k

c

e

h

c

e

b

t

s

u

m

.

l

o

r

t

n

o

c

t

i

m

i

l

h

g

i

h

d

n

a

l

o

r

t

n

o

c

2. VERIFY PRIMARY CONTROL FEATURES

using procedures outlined in Instructions furnished
with control or instructions as follows:

a. FEATURES

AND CONTROLS

i.

The R7184 is a microprocessor-based
control. The indicator light provides
diagnostic information for lockout, recycling
and patented cad cell status. There is a
manual reset button to exit the Lockout
Mode and enter the Idle Mode (see Figure
28).

ii. Pump Priming Cycle: To facilitate purging

air from the oil lines and fi lters, the R7184
can be placed in a purge routine by pressing
and releasing the reset button during the
safety check, delayed valve-on, ignition or
carry-over periods.

iii. Limited

Recycle: This feature limits the

number of recycle trials (for each call
for heat) to a maximum of three trials. If
the fl ame is lost three times and does not
successfully satisfy a call for heat, the
R7184 locks out.

iv. Limited Reset (Restricted Mode): In order

to limit the accumulation of unburned oil in
the combustion area, the control can only be
reset three times. The reset count returns to
zero each time a call for heat is successfully
completed.

To reset from Restricted Mode: Press and

hold the reset button for 30 seconds.
When

the

LED

fl ashes twice, the device

has

reset.