LEDs on the nonport side of the Brocade 7800

The nonport side of the Brocade 7800 has the following LEDs:

One power supply LED next to the AC power switch on each fan and power supply
assembly. See

Figure 3

on page 5 for a diagram of the non-port side of the switch.

Table 5

describes the LEDs on the nonport side of the Extension Switch.

TABLE 5

Nonport Side LED patterns during normal operation

LED Name

LED Color

Status of Hardware

Recommended Action

Power Supply/
Fan Status

No light

Power supply is not seated correctly. Verify that the power supply is

seated correctly.

Steady green

System is on and power supplies are
functioning properly.

No action required.

Flashing green

Fault has occurred in the FRU.

Try the following:

Check the power cable
connection.

Verify that the power supply is
powered on.

Run psShow and fanShow
commands to determine the
source of the fault.

Replace the FRU.