SECTION V

FREESTANDING MOBILE HOME

INSTALLATION

NOTE: See page 26 for clearances for Mobile Home.

FLOOR PROTECTION

Floor protector must be 3/8" minimum thickness non-combustible material or equivalent. With
the floor protector or hearth extension material specified as one layer of 2" thick brick with a
K* factor of 5.0, you may use alternate materials as long as the K factor(s) is calculated as
follows:

FORMULA: Required thickness = (K of alternate material/K of millboard) x (thickness

of millboard)

EXAMPLE: An alternate inorganic non-combustible millboard with a K of .9375

would require a thickness as follows:

Required thickness = (.9375/5.0) x 2 in.

= 3/8 inch


K FACTORS OF ALTERNATE MATERIALS

Material

K

Required

Thickness

Ceroform

126

.21

1/8"

Limestone

8.0

3.2"

Concrete

8.0

3.2"

Sandstone

13.0

5.2"

Marble

18.0

7.2"


A hearth extension or floor protector thickness above 4" is generally not acceptable due to cost,
floor load capacity, and look. The alternate we recommend is using Ceroform No. 126
millboard 1/8" minimum and putting any type decorative brick or stone (any thickness) on top
of it.

*The “K” factor represents the thermal conductivity of a material and is the time rate of heat
flow through a homogeneous material under steady-state conditions, through unit area, per unit
temperature gradient in the direction perpendicular to a surface.

CHIMNEY

These models are designed for connection to Simpson Dura-vent, Metal Fab and Ameritec
HT-103 2100º F pipe.