PHYSICAL DATA — 580D090-150

UNIT SIZE 580D

090

102

120

150

NOMINAL CAPACITY (tons)

7

1

⁄

2

8

1

⁄

2

10

12

1

⁄

2

OPERATING WEIGHT (lb)

Unit

Al/Al*

870

880

1035

1050

Al/Cu*

881

896

1057

1077

Cu/Cu*

893

907

1080

1100

Economizer

Durablade

44

44

44

44

Parablade

62

62

62

62

Roof Curb†

143

143

143

143

COMPRESSOR

Hermetic

Quantity

2

2

2

2

No. Cylinders (per Circuit)

2

2

2

2

Oil (oz)

50 ea

50 ea

50 ea

54 ea

REFRIGERANT TYPE

R-22

Expansion Device

Acutrol™ Feed Device

Operating Charge (lb-oz)

Circuit 1

4-13

6-14

5-13

8-10

Circuit 2

4-14

6- 3

5-14

8- 8

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

20.50

18.00

17.42

25.00

CONDENSER FAN

Propeller Type

Nominal Cfm

6500

6500

7000

7000

Quantity...Diameter (in.)

2...22

2...22

2...22

2...22

Motor Hp...Rpm

1

⁄

4

...1100

1

⁄

4

...1100

1

⁄

4

...1100

1

⁄

4

...1100

Watts Input (Total)

600

600

600

600

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

Rows...Fins/in.

3...15

3...15

3...15

4...15

Total Face Area (sq ft)

8.0

8.0

10.0

11.1

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...15 x 15

1...15 x 15

1...15 x 15

1...15 x 15

Alt

1...15 x 15

—

1...15 x 15

1...15 x 15

Type Drive

Std

Belt

Belt

Belt

Belt

Alt

Belt

—

Belt

Belt

Nominal Cfm

3000

3400

4000

5000

Motor Hp

Std

—

—

—

—

Alt

—

—

—

—

Maximum Continuous Bhp

Std

2.40

2.40

2.40

4.20

Alt

—

—

2.90

5.25

Motor Frame Size

Std

56

56

56

56

Alt

—

—

56

56

Nominal Rpm High/Low

—

—

—

—

Fan Rpm Range

Std

590-840

685-935

685-935

860-1080

Alt

685-935

—

835-1085

900-1260

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

2.8/3.8

2.8/3.8

4.0/5.0

Alt

2.8/3.8

—

3.4/4.4

3.1/4.1

Nominal Motor Shaft Diameter (in.)

Std

5

⁄

8

5

⁄

8

5

⁄

8

7

⁄

8

Alt

—

—

7

⁄

8

7

⁄

8

Fan Pulley Pitch Diameter (in.)

Std

7.0

7.0

7.0

8.0

Alt

7.0

—

7.0

5.9

Nominal Fan Shaft Diameter (in.)

—

—

—

—

Belt, Quantity...Type...Length (in.)

Std

1...A...49

1...A...49

1...A...49

1...A...52

Alt

1...A...49

—

1...A...49

1...BX...46

Pulley Center Line Distance (in.)

Std

16.75-19.25

16.75-19.25

15.85-17.50

15.85-17.50

Alt

16.75-19.25

—

15.85-17.50

15.85-17.50

Speed Change per Full Turn of

Std

50

50

50

44

Movable Pulley Flange (rpm)

Alt

50

—

50

50

Movable Pulley Maximum Full Turns

Std

5

5

5

5

From Closed Position

Alt

5

—

5

6

Factory Setting

Std

5

5

5

5

Alt

5

—

5

5

Factory Speed Setting (rpm)

Std

590

685

685

860

Alt

685

—

835

960

Fan Shaft Diameter at Pulley (in.)

1

1

1

1

LEGEND

Al

— Aluminum

Bhp — Brake Horsepower
Cu

— Copper

*Evaporator coil fin material/condenser coil fin material. Contact your

local representative for details about coated fins.

†Weight of 14-in. roof curb.

**Rollout switch lockout is manually reset by interrupting power to unit

or resetting thermostat.

††Requires an optional or accessory Controls Upgrade Kit.

NOTE: The 580D036-150 units have a loss-of-charge/low-pressure
switch (accessory or option) located in the liquid line.