PERFORMANCE DATA (cont)

EVAPORATOR-FAN MOTOR PERFORMANCE

UNIT

EVAPORATOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

580D036

Standard

208/230

0.34

440

2.9

460

1.4

575

1.4

Alternate

208/230

1.00

1000

5.4

460

2.3

575

2.3

580D048

Standard

208/230

0.75

850

3.5

460

1.8

575

1.8

Alternate

208/230

1.00

1000

5.4

460

2.3

575

2.3

580D060

Standard

208/230

1.20

1340

5.9

460

3.2

575

3.2

Alternate

208/230

1.80

1921

8.9

460

4.7

575

4.7

580D072

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D090

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D102

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D120

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

Alternate

208/230

2.90

2615

7.9

460

3.6

575

3.6

580D150

Standard

208/230

4.20

3775

11.1

460

5.0

575

5.0

Alternate

208/230

5.25

4400

15.0

460

7.4

575

7.4

579F180

Standard

208/230

4.25

3775

10.5

460

4.8

579F216

Standard

208/230

5.90

5180

15.8

460

7.9

579F240

Standard

208/230

8.70

7915

22.0

460

9.50

8640

13.0

579F300

Standard

208/230

10.20

9510

28.0

460

11.80

11,000

14.6

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the

full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.

NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.

55