Accusensor iii sensor, Thermostat, Cont a cts sho wn in high enthalpy – Bryant 580D User Manual

Page 16: Or unpowered st at e, Tr tr1 24v ac

Advertising
background image

OPTIONS AND ACCESSORIES (cont)

ACCUSENSOR™ II

CONTROL

(036-150 Only)

MINIMUM

POSITION

OPEN

3

1

T

P

P1

T1

4

2

5

S

S

O

D

C

TR

B

REV

. B

198818A

%

H

U

M

I

D

I

T

Y

90

70

60

30

10

D

C

B
A

60

65

70

75

55

50

85

80

DAMPER

DAMPER

CLOSED

OPEN

OUTDOOR TEMP

.

°

F

REV.

97-3672

CW–SETPOINTS–CCW

CONT

A
CTS SHO

WN IN HIGH ENTHALPY

RUSH A

T

24V

AC

3 mA

MIN.

A

T

1

1

VDC

CONT

ACT RA

TINGS: 1.5A

RUN, 3.5A

IN

OR UNPOWERED ST

AT

E

1

2

3

TR

TR1

24V

AC

ENTHALPY

CONTROL

ACCUSENSOR III

SENSOR

+

Accusensor economizer controls help provide efficient, economical
economizer operation. Accusensor II solid-state enthalpy control in-
cludes the logic and one sensor to calculate both dry- and wet-bulb of
the outdoor air to provide an accurate enthalpy reading on 036-150
units. It then decides when to energize the economizer based on this
reading. The 180-300 unit economizer provides the decision-making
function internally, and requires one Accusensor III sensor for solid-state
enthalpy sensing. A second Accusensor III sensor (required for all units
for differential enthalpy sensing) compares outdoor temperature and hu-
midity to return-air temperature and humidity and determines the most
economical mixture of air (purchased in addition to enthalpy control
[sizes 036-150] or to first solid-state enthalpy sensor [sizes 180-300] for
differential enthalpy sensing).

POWER EXHAUST (180-300 SHOWN)

When used with accessory/optional economizer, the power exhaust
accessory helps to relieve building over-pressurization.

NOTE: This accessory is not available with horizontal supply
adapter.

THERMOSTAT

H

C

Thermostat (24 v) provides one- or 2-stage cooling for control of unit.
Matching subbases are available with or without tamperproof
switches and automatic changeover.