ARI* CAPACITY RATINGS

UNIT 580D

NOMINAL

TONS

STANDARD

CFM

NET COOLING

CAPACITY

(Btuh)

TOTAL

kW

SEER†

SOUND

RATING

(Bels)

Belt Drive

Direct Drive

036

3

1200

35,000

4.0

10.0

9.7

8.2

048

4

1600

47,000

5.5

10.0

9.7

8.2

060

5

2000

57,000

6.7

10.0

9.7

8.2

UNIT

NOMINAL

TONS

STANDARD

CFM

NET COOLING

CAPACITY

(Btuh)

TOTAL

kW

EER

SOUND

RATING

(Bels)

IPLV

580D072

6

2100

72,000

8.0

9.0

8.2

**

580D090

7

1

2

2800

85,000

9.6

8.9

8.6

9.35

580D102

8

1

2

3000

99,000

11.0

9.0

8.6

9.00

580D120

10

4000

117,000

13.0

9.0

8.8

9.35

580D150

12

1

2

4500

145,000

16.1

9.0

8.8

9.20

579F180

15

5250

178,000

20.7

8.6

8.8

10.70

579F216

18

6000

190,000

21.3

8.9

9.0

9.20

579F240

20

6200

222,000

25.5

8.6

9.5

8.80

579F300

25

7200

268,000

31.4

8.5

9.5

8.40

LEGEND

Bels

Sound Levels (1 bel = 10 decibels)

db

Dry Bulb

EER

Energy Efficiency Ratio

IPLV

Integrated Part-Load Values

SEER — Seasonal Energy Efficiency Ratio
wb

Wet Bulb

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 65,000 Btuh or less.

**The IPLV applies only to two-stage cooling units.

NOTES:
1. Rated in accordance with ARI Standards 210/240-89 (for sizes 036-120) or 360-89 (for sizes 150-240) and 270-89.
2. The 579F300 is beyond the scope of the ARI certification program.
3. ARI ratings are net values, reflecting the effects of circulating fan heat.
4. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.