Bryant 580D User Manual

Page 20

Advertising
background image

BASE UNIT DIMENSIONS — 579F240,300

UNIT
579F

CORNER WEIGHT*

DIMENSION

X

A

B

C

D

lb

kg

lb

kg

lb

kg

lb

kg

ft-in.

mm

240

520 235 508 230 532 241 640 290

3-2

965

300

527 239 545 247 578 262 600 272

3-7

1092

*Weights are for unit only (aluminum plate fins) and do not include op-

tions or crating.

NOTES:
1. Dimensions in (

) are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. Ductwork to be attached to accessory roof curb or

adapter only.

5. Minimum clearance:

a. Rear: 7

Ј

0

Љ

(2134) for coil removal. This dimension

can be reduced to 4

Ј

0

Љ

(1219) if conditions permit

coil removal from the top.

b. 4

Ј

0

Љ

(1219) to combustible surfaces, all four sides

(includes between units).

c. Left side: 4

Ј

0

Љ

(1219) for proper condenser coil

airflow.

d. Front: 4

Ј

0

Љ

(1219) for control box access.

e. Right side: 4

Ј

0

Љ

(1219) for proper operation of

damper and power exhaust (if so equipped).

f. Top: 6

Ј

0

Љ

(1829) to assure proper condenser fan

operation.

g. Bottom: 14

Љ

(356) to combustible surfaces (when not

using curb or adapter).

h. Control box side: 3

Ј

0

Љ

(914) to ungrounded surfaces

(non-combustible).

i. Control box side, 3

Ј

6

Љ

(1067) to block or concrete

walls, or other grounded surfaces.

j. Local codes or jurisdiction may prevail.

6. With the exception of clearance for the condenser coil

and the damper/power exhaust as stated in Note No. 5,
a removable fence or barricade requires no clearance.

7. Dimensions are from outside of corner post. Allow

0

Ј

-

5

16

Љ

(8) on each side for top panel drip edge.

8. Do not locate adjacent units with the discharge facing

economizer inlet.

20

Advertising