blower motor stops. The unit is in a ‘‘standby’’ condition, waiting
for the next ‘‘call for cooling’’ from the room thermostat. The 5
minute compressor delay also applies to heat pump heating mode.

ELECTRICAL DATA & SCHEMATICS—ICM FIOP

I.

PHYSICAL DATA & ELECTRICAL SCHEMATICS

Use the Physical Data and Electrical Tables on the following pages
for information that applies to Bryant Puron® units with the ICM
indoor motor FIOP.

AIRFLOW & TEMPERATURE RISE TABLES—ICM
FIOP

II.

TABLES FOR SYSTEM SET-UP

Use the Airflow and Temperature Rise Tables on the following
pages for information that applies to Bryant Puron® units with the
ICM indoor motor FIOP.

CARE AND MAINTENANCE

Indoor Blower and Motor
NOTE: All motors are pre-lubricated. Do not attempt to lubricate
these motors. For longer life, operating economy, and continuing
efficiency, clean accumulated dirt and grease from the blower
wheel and motor annually.

WARNING:

Disconnect and tag electrical power to the

unit before cleaning and lubricating any blower motor
and wheel. On units with gas heat, turn off the gas supply
before disconnecting the electrical power. Failure to
adhere to this warning could cause serious injury or
death.

To clean the blower motor and wheel:

1. 1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. Carefully pivot blower access panel outward towards the

electrical box. Route wiring above blower access panel.

c. Disconnect the 5 and 16 pin plugs at the blower motor.

d. On all units, remove blower assembly from unit. Re-

move screws securing blower to vertical partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.

e. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 583B

024040

024060

030040

030060

036060

036090

042060

042090

NOMINAL CAPACITY (ton)

2

2

2-1/2

2-1/2

3

3

3-1/2

3-1/2

OPERATING WEIGHT (lb.)

290

290

313

313

321

321

382

382

COMPRESSORS

Quantity

Scroll

1

REFRIGERANT (R-410A)

Quantity (lb.)

5.0

5.0

5.5

5.5

6.9

6.9

9.0

9.0

REFRIGERANT METERING DEVICE

Orifice ID (in.)

Check-Flo-Rater™ Piston

.057

.057

.057

.057

.065

.065

.070

.070

CONDENSER COIL

Rows...Fins/in.

Face Area (sq ft)

1...17

10.9

1...17

10.9

1...17

12.7

1...17

12.7

2...17

9.1

2...17

9.1

2...17

12.3

2...17

12.3

CONDENSER FAN

Nominal Cfm

Diameter (in.)

Motor HP (Rpm)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

EVAPORATOR COIL

Rows...Fins/in.

Face Area (sq ft)

3...15

3.7

3...15

3.7

3...15

3.7

3...15

3.7

3...15

3.7

3...15

3.7

3...15

4.7

3...15

4.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)

Size (in.)

Motor (HP)

800

10 X 10

1/2

800

10 X 10

1/2

1000

10 X 10

1/2

1000

10 X 10

1/2

1200

11 X 10

3/4

1200

11 X 10

3/4

1400

11 X 10

3/4

1400

11 X 10

3/4

FURNACE SECTION*

Burner Orifice No. (Qty...Drill Size)

Natural Gas

Burner Orifice No. (Qty...Drill Size)

Propane Gas

2...44
2...50

2...38
2...46

2...44
2...50

2...38
2...46

2...38
2...46

3...38
3...46

2...38
2...46

3...38
3...46

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-

PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway

20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

—12—